Lenze EDB9300UES User Manual
Page 17

Technical Data
12
BA8230
•
Mechanical use
prEN50178:1994/IPA90 DIN IEC86
(Vibration)
T.2-6 10 ... 150 Hz
•
Electromagnetic
compatibility
3)
:
- Interference resistance
To IEC1800-3 (IEC22G/21/CDV), EN50082-2,
suitable for use in an industrial environment
- Radiated interference
To IEC1800-3 (IEC22G/21/CDV)
- industrial mains supply
AC mains choke
4)
- public supply network
Additional RFI filter
4)
EN50081-2, limit to EN55011 Group 1 Class A:
Mains choke and RFI filter
4)
EN50081-1, limit to EN55011 Group 1 Class B:
Mains choke, RFI filter and Motor filter
4)
1)
Adequate convection cooling must be provided for the 8230 frequency inverter control
electronics. No heat build up inside the 8230 frequency inverter.
2)
No salt spray mist.
3)
Connection to earthed network
4)
see section 3.7 for optional measures
•
Pulse frequency
adjustable
- Standard
3 kHz
- Maximum
Up to 6 kHz
For a chopping frequency of f
p
=6 kHz, a power reduction to 1.5 rated current is
required.
•
Servicing
Data memory battery replacement required,
see section 7.1
Fan replacement recommended, see section 7.2
Check power connection screws, see section 7.3
Show/Hide Bookmarks