4 fuse circuit breakers, 5 mains contactor, Fuse circuit breakers – Lenze EDB9300UES User Manual
Page 28: Mains contactor

Technical Data
BA8230
23
2.4.1.3 Line fuses for
Installation instructions for a 3AC 8230 frequency inverter connection in the
operation class gL and
customer’s low voltage distribution system:
cable cross-sections
The NH fuses recommended for operation class gL and the cable cross-sections to be
used for 8230 frequency inverter 3AC mains connections are shown in the following
table. Minimum cross-sections for mains supplies cables with PVC insulation
according to EN 60204-1:1992 are given for an ambient temperature of
ϑ
= 40 °C and
laying method E.
8230 frequency inverter
type
Unit output current
Recommended fuse
gL characteristics
Recommended cable
cross-sections for PVC
insulated copper cable
1.2 x Rated
current
1.5 x Rated
current
Max. current
for 60 s
Type
3-phase cables
NYY/ NYM
[A]
[A]
[A]
8231
257
216
324
315 A Gr.2
2x3x95 mm²
8232
304
257
365
355 A Gr.2
2x3x120 mm²
8233
396
325
488
400 A Gr.2
2x3x150 mm²
8234
483
400
600
500 A Gr.3
2x3x185 mm²
Table 10: 8230 frequency inverter AC line fuses
2.4.1.4 Fuse circuit breakers
The above semiconductor fuses (aR-Characteristics) with 100 mm length to
DIN 43 653 can be installed as an alternative to fuse bases in conjunction with the
hand-operated fuse circuit breaker.
This creates a separation point in the 3AC mains supply and all poles of the
semiconductor fuses can be switched.
2.4.1.5 Mains contactor
Contactors 3 AC 400 V, 50/60 Hz
On 3AC mains supplies which include (automatic) on/off switching of the mains
voltage at the 8230 frequency inverter input (eg. 8230 frequency inverter units with
optional brake chopper and braking resistor), 3-phase contactors according to the
following tables are used.
Important! Note the mains contactor control voltage!
8230 frequency
inverter type
Unit output current
Contactors 3 AC
1.2 x Rated
current
1.5 x Rated
current
Max. current
for 60 s
Type
[A]
[A]
[A]
8231
257
216
324
LS247.22
8232
304
257
365
LS247.22
8233
396
325
488
CA-5-550A
8234
483
400
600
CA-5-550A
Table 11: Mains contactors
Mains contactors and accessories are stated for 400 V, 50/60 Hz mains voltage.