2 series of types, Series of types – Lenze EDB9300UES User Manual
Page 11

Technical Data
6
BA8230
2.2 Series of types
8230 frequency inverter for 3-phase AC connection
8230 frequency inverter 150 ... 275 kVA, 3AC 380 ... 480 V
Processor-controlled pulse inverter with field-orientated control concept for continuous
low-loss speed adjustment of standard AC motors.
8230 frequency
inverter
Frame
size
Unit input current,
Unit output current
mains current
5)
1.2 x rated
current
1)
1.5 x rated
current
2)
Max. current
60 s
3)
Supply voltage
eff [A]
[A]
[A]
[A]
8231
8
195 (230)
257
216
324
3 AC 50/60Hz
8232
8A
230 (270)
304
257
365
380 ... 460 V
8233
9
290 (360)
396
325
488
+10/-15 %
8234
9A
360 (430)
483
400
600
...480 V
+6/-15 %
Table 1: 8230 frequency inverter series
1)
Rated current with overload capacity 1.2 x rated current
2)
Rated current with overload capacity 1.5 x rated current
3)
Max. current for max. 60 s overload, cycle time 600 s
4)
Mains commutation choke not included in scope of supply.
5)
The details for the mains current with the standard mains choke are based on a
mains short circuit capacity in relation to the inverter power of 100 : 1 at unit output
current = rated current. Values in brackets are valid for 1.2 rated current.
Frame size
Dimensions
Weight
H x W x D [mm]
ca. [kg]
8
1049 x 495 x 419
90
8A
1224 x 495 x 419
90
9
1499 x 495 x 419
140
9A
1674 x 495 x 419
140
Table 2: 8230 frequency inverter frame sizes
Scope of supply: Build-in unit, IP20
Show/Hide Bookmarks