Setting of all important parameters
EDK71MMXXX−010 DE/EN/FR 5.0
L
96
Before commissioning, set important operating parameters with the potentiometers and the stepping
switch:
−24−
l
the rated motor current with the stepping switch
l
the acceleration time with potentiometer "T"
l
the starting voltage with potentiometer "U
0
"
Stepping switch [S]
Lenze motor power with mains voltage
Comment
Position
Rated current
3/PE 230 VA
C
3(/N)/PE 400
VAC
3(/N)/PE 500
VAC
0
–
–
–
–
No I
2
t monitoring
1
1.0 A
–
0.25 kW
0.37 kW
2
1.4 A
–
0.37 kW
0.55 kW
3
1.8 A
0.25 kW
0.55 kW
0.75 kW
4
2.4 A
0.37 kW
0.75 kW
1.1 kW
5
3.0 A
0.55 kW
1.1 kW
1.5 kW
6
4.0 A
0.75 kW
1.5 kW
2.2 kW
7
5.5 A
1.1 kW
2.2 kW
3.0 kW
8
7.0 A
1.5 kW
3.0 kW
4.0 kW
9
9.5 A
2.2 kW
4.0 kW
5.5 kW
Setting
Comment
1.
Set the rated motor current with the
stepping switch
Lenze setting: 1 = 1.0 A
start032
1.4 A
1.8 A
2.4
A
3.0 A
4.0
A
5.5 A
7.0 A
9.5
A
OFF
1.0
A
0 1 2
3
45
67
8
9
l
See also
^ 79
l
Use the hand terminal to
check or change the
setting in C0120
2.
Set the acceleration time t
ir
with
potentiometer T"
Lenze setting: approx. 1.5 s
start012
0
3.00 s
Use the hand terminal to
check or change the setting
in C0012
3.
Set the starting voltage U
0
with
potentiometer U
0"
Lenze setting: approx. 50 %
start008
0
100.0 %
l
With U
0
= 100 %, the
acceleration time t
ir
is
deactivated
l
Use the hand terminal to
check or change the
setting in C0016
start028
100%
0
0
t
Uout
Ustart