Commissioning, Code table – Lenze EDK71MMXXX−010 User Manual
Page 110

7
Commissioning
Code table
EDK71MMXXX−010 DE/EN/FR 5.0
L
110
Code
IMPORTANT
Setting options
No.
Selection
Lenze
Designation
C0003
v
Save parameter
non−volatile
1
0
Do not save parameter in EEPROM
Data loss after mains
disconnection
1
Always save parameter in EEPROM
l
Active after every mains
connection
l
Cyclical changing of
parameters via bus
module is not allowed
3
Save separate basic setting in
EEPROM
Subsequently save with
parameter set 1 with
C0002 = 9 as separate
basic setting
C0004
Bar graph
display
54
1
{code no.}
989
l
Bar graph display shows
the selected value in %
after mains connection
l
Range
−180 % ... +180 %
54 = apparent current of motor 1 (C0054)
C0005
v
Fixed
configuration of
input signals
0
Code is individually
adjustable in four
parameter sets
0
All digital input signals are supplied
from terminal strip X3
Sets C0410/x = Lenze
setting
200
All digital input signals are fed from
fieldbus function module to FIF
(e.g. INTERBUS or PROFIBUS−DP)
Sets C0410/x = 200
255
All digital input signals are fed from
fieldbus function module to FIF
(e.g. INTERBUS or PROFIBUS−DP)
C0410/x was freely
configured
C0006
v
uSEr
Transfer
HW/*hand
terminal
0
C0012
C0016
C0120
l
Parameter setting of
codes via:
– PU: Potentiometer
"U
0
" for starting
voltage
– PT: Potentiometer "T"
for acceleration time
– S: Stepping switch for
rated motor current
– H: Hand terminal
l
With the parameter
setting via
potentiometer/switch,
you can check the
setting via hand terminal
l
When switching to hand
terminal, the values set
with PU, PT and S are
transferred.
0
PT
PU
S
1
PT
PU
H
2
PT
H
S
3
PT
H
H
4
H
PU
S
5
H
PU
H
6
H
H
S
7
H
H
H