Commissioning, With hand terminal – Lenze EDK71MMXXX−010 User Manual
Page 102
7
Commissioning
With hand terminal
EDK71MMXXX−010 DE/EN/FR 5.0
L
102
The
user menu is set to all codes at the factory to allow for commissioning a standard application:
)
Note!
Settings for "Motor 2" are not relevant for the starttec "Motor starter
type 1"! (Corresponding information applies only to the starttec "Motor
starter type 2" for operation with 2 motors.)
Code
Designation
Lenze setting
C0054 Apparent motor current of
motor 1
Display only
C0055 Apparent motor current of
motor 2
Display only
C0006 Transfer HW/hand terminal
0
Setting the acceleration time (C0012) and starting voltage
(C0016) via potentiometer, setting the rated motor current
(C0120) via stepping switch
C0120 Rated current
Rated motor current for I
2
t monitoring
1 Motor 1
Accepts the value from the stepping switch:
l
If C0006 = 0, 2, 4, 6:
– Display only
l
If C0006 = 1, 3, 5, 7:
– Rated current can be set via C0120
2 Motor 2
C0410 Configuration of digital input
signals
1 Motor 1 start/stop
1
X3/E1
2 Motor 2 start/stop
2
X3/E2
3 Brake control
3
X3/E3
4 ... 24
255
Not assigned
C0415 Configuration of digital
output signals
1 X3/A1
3
Status of motor 1
2 X3/A2
4
Status of motor 2
3 X3/A3
5
Status of brake
4 X3/A4
25
TRIP error message
5 ... 6 AS−I output bit
255
Not assigned
C0012 Motor voltage acceleration
time
Time for voltage change U
0
... U
mains
1 Motor 1
Accepts the value from potentiometer "T"
l
If C0006 = 0, 1, 2, 3:
– Display only
l
If C0006 = 4, 5, 6, 7:
– Acceleration time can be set via C0012
2 Motor 2
C0423 Delay time of "Release
brake"
0.00 s
C0424 Delay time of "Apply brake"
0.00 s
C0002 Parameter set management
See code table