Commissioning, Code table – Lenze EDK71MMXXX−010 User Manual
Page 112
7
Commissioning
Code table
EDK71MMXXX−010 DE/EN/FR 5.0
L
112
Code
IMPORTANT
Setting options
No.
Selection
Lenze
Designation
C0015
s
Manual setting
of operating
mode
0
0
Automatic recognition of the
operating mode
From software version
2.0 onwards
starttec recognises whether
the wiring was performed
for multi−motor operation or
for reversal of the rotation
direction. For operation with
a pole−changing motor or
with motors < 250 W, the
operating mode must be
set manually in C0015.
1
Ignoring the automatic recognition
Operating mode = operation with
one motor or multi−motor operation
2
Ignoring the automatic recognition
Operating mode = reversal or
operation with pole−changing motor
This setting is essential
when operating with
motors < 250 W in the
operation mode
"reversal"! Otherwise,
the starttec may be
destroyed.
C0016
Starting voltage
U
0
0.0
{0.1 %}
100.0
= deactivated
acceleration
time
1 Motor 1
а
а
Accepts the value from
potentiometer "U
0
"
l
If C0006 = 0, 1, 4, 5:
– Display only
l
If C0006 = 2, 3, 6, 7:
– Starting voltage
adjustable via C0016
2 Motor 2
а
а
Accepts the value from
potentiometer "T"
l
If C0006 = 0, 1, 4, 5:
– Display only
l
If C0006 = 2, 3, 6, 7:
– Starting voltage
adjustable via C0016
C0040
v
Inhibit starttec
0
starttec inhibited (CINH)
starttec can only be
released if X3/28 = HIGH
1
starttec released (CINH)
C0043
v
TRIP reset
0
Currently no fault
Reset active fault with
C0043 = 0
1
Active fault
C0052
Service code
Potentiometer "T"
Changes only through
Lenze Service!