Commissioning
Code table
7
EDK71MMXXX−010 DE/EN/FR 5.0
113
L
Code
IMPORTANT
Setting options
No.
Selection
Lenze
Designation
C0054
uSEr
Apparent
current of
motor 1
0
{A}
50 Display only
C0055
uSEr
Apparent
current of
motor 2
0
{A}
50 Display only
C0061
Housing
temperature
0
{
°C}
255 Display only
l
If > +80 °C:
– starttec sets TRIP
OH
C0093
Device type
4020
Display only
C0094
Reserved
C0099
Software
version
x.y
Display only
x = main version, y = index
C0119
v
Configuration of
motor
temperature
monitoring (PTC
input)
1
0
PTC input inactive
Configure signal output in
C0415
1
PTC input active, TRIP occurs
2
PTC input active, warning occurs
C0120
uSEr
Rated motor
current
1.0
{0.1 A}
9.5 See nameplate of motor
1 Motor 1
а
а
Accepts the value from
the stepping switch
l
If C0006 = 0, 2, 4, 6:
– Display only
l
If C0006 = 1, 3, 5, 7:
– Rated motor current
adjustable via C0120
2 Motor 2
à
C0121
Tripping class
Tripping characteristic see
^ 79
1 Motor 1
2
Tripping class 10
2 Motor 2
2
Tripping class 10
0
I
2
t monitoring switched off
1
Tripping class 10A
2
Tripping class 10
3
Tripping class 20
4
Tripping class 30
C0122
Mains phase
failure message
0
0
TRIP
1
Warning
C0123
Message I
2
t
overload
0
0
TRIP
Change becomes effective
only after next release of
starttec
1
Warning