Electrical installation, Connection of as interface – Lenze EDK71MMXXX−010 User Manual
Page 93
Electrical installation
Connection of AS interface
5
EDK71MMXXX−010 DE/EN/FR 5.0
93
L
Configuration
Data bits to starttec:
In C0410 (selection 6, 7, 8), you can assign the data bits D0, D1 and D2 to internal digital signals.
Data bits from starttec:
In C0415, subcode 5 and 6, you can assign internal digital signals to data bits D0 and D1.
Example:
The starttec will be released via AS−I and a brake motor will then be started. The starttec will report
back the status of the motor and the brake via AS−I.
Data bits to starttec:
AS−I configuration
starttec
parameter setting
Comment
Bit
Command
D0
Release/inhibit starttec
C0410/10 = 6
D0 = 1:
starttec released
(requirement: terminal X3/28 = HIGH)
D0 = 0:
starttec inhibited
D1
Start/stop motor
C0410/1 = 7
D1 = 1:
Start motor
D1 = 0:
Stop motor
D2
Release/apply brake
C0410/3 = 8
D2 = 1:
Release brake
D2 = 0:
Apply brake
Data bits from starttec:
AS−I configuration
starttec
parameter setting
Comment
Bit
Message
D0
Status of motor
C0415/5 = 3
D0 = 1:
Motor is running
D0 = 0:
Motor is stopped
D1
Status of brake
C0415/6 = 5
D1 = 1:
Brake is released
D1 = 0:
Brake is applied