Function library lenzeiosystem.lib, Appendix – Lenze DDS Function library IOSystem User Manual
Page 78
6.3
Signal functions for analog inputs and outputs EPM−T330
Function library LenzeIOSystem.lib
Appendix
6−8
L
LenzeIOSystem.lib EN 1.7
Parameter
bytes 2/3/4/5
Tolerance
1)
Format
Signal range
Signal function
04
h
Current signal output
4 ... 20 mA
+4.00
0
{0.01 mA}
{1 dec}
+20.00
+16384
B
±0.8 % of limit value
Lower range limit:
+0.00 mA
−4096
dec
Upper range limit:
+24.00 mA
+20480
dec
06
h
Current signal output
0 ... 20 mA
0.00
0
{0.01 mA}
{1 dec}
+20.00
+16384
B
±0.6 % of limit value
Lower range limit:
−
Upper range limit:
+25.00 mA
+20480
dec
0B
h
Current signal output
(complement on two)
±20 mA
−20.00
−27648
{0.01 mA}
{1 dec}
+20.00
+27648
A
±0.3 % of limit value
Lower range limit:
−23.52 mA
−32512
dec
Upper range limit:
+23.52 mA
+32511
dec
0C
h
Current signal output
(complement on two)
4 ... 20 mA
+4.00
0
{0.01 mA}
{1 dec}
+20.00
+27648
A
±0.8 % of limit value
Lower range limit:
+0.00 mA
−6912
dec
Upper range limit:
+22.81 mA
+32511
dec
0E
h
Current signal output
0 ... 20 mA
0.00
0
{0.01 mA}
{1 dec}
+20.00
+27648
A
±0.6 % of limit value
Lower range limit:
−
Upper range limit:
+23.52 mA
+32511
dec
FF
h
Analog output deactivated
1)
The tolerance values were established at 25 °C ambient temperature and 15 conversions/s. No sensor
inaccuracies were taken into consideration.