L_IOParSSIModule − Parameterisation function
Function library LenzeIOSystem.lib
Function blocks
4−12
L
LenzeIOSystem.lib EN 1.7
4.5
L_IOParSSIModule − Parameterisation function
The SSI interface (SSI = Synchronous Serial Interface) is a synchronously clocked interface.
Function block L_IOParSSIModule converts the serial information of the measured values into
parallel information that is subsequently supplied to the control system.
byFunction_Baudrate
bFunction_Code
L_IOParSSIModule
bExecute
byNodeAdr
nState
CTRL
byAnalogModuleNo
bFunction_Hold
EPM-T110
Ixxxh
bFunction_SetDigitalOut
ð Inputs
(Variable type: VAR_INPUT)
Variable name
Data type
Information/possible settings
bExecute
Bool
Execute write request
FALSE
ä TRUE Write request is executed
byNodeAdr
Byte
Device address: 1 − 63
byAnalogModuleNo
Byte
Slot number
·
The first analog module installed is assigned slot number 1.
·
A maximum of 9 modules may be plugged.
byFunction_Baudrate
Byte
Baud rate setting
0 300 kbps
1 100 kbps
2 300 kbps
3 600 kbps
4 300 kbps
bFunction_Code
Bool
Coding
Default 0 Binary code
1 Gray code
bFunction_Hold
Bool
Hold function
0 Not active
1 Active
bFunction_SetDigitalOut
Bool
Digital outputs
0 Not active
1 Active