Function library lenzeiosystem.lib, Function blocks – Lenze DDS Function library IOSystem User Manual
Page 42

4.9
L_IOParPDO610 − Parameterisation function
Function library LenzeIOSystem.lib
Function blocks
4−24
L
LenzeIOSystem.lib EN 1.7
(Variable type: VAR_INPUT)
ð Inputs
Variable name
Information/possible settings
Data type
wCobID_TxPDO6
...
wCobID_TxPDO10
WORD
Setting identifiers
Default values: input wiring = 0
TxPDO = receive identifiers from the I/O system
Identifiers can be optionally set by value selection.
If the input wiring is "0", the identifiers are composed as follows.
Note: The basic identifiers are not settled in the pre−assigned area of the standard
system bus.
ID range: 384−831
By this, crossovers of the ID with the free CAN objects which the IO−lib is based on
are avoided.
TxPDOX
Identifier =
Basic ID +
Node address
TxPDO6
863
861
2
TxPDO7
866
TxPDO8
871
TxPDO9
876
TxPDO10
881
byTransmissionType_TxPDO6
...
byTransmissionType_TxPDO10
Byte
Transmission mode
0 Event−controlled
1 Time−controlled
2 Event−controlled with superimposed cycle time
tinhibitTime_TxPDO6
...
tinhibitTime_TxPDO10
Time
Inhibit time: t = 0 − 65535 ms
tCyceTime_TxPDO6
...
tCyceTime_TxPDO10
Time
Cycle time: t = 0 − 65535 ms