Function library lenzeiosystem.lib, Function blocks – Lenze DDS Function library IOSystem User Manual
Page 28
4.4
L_IOParAlAOModule − Parameterisation function
Function library LenzeIOSystem.lib
Function blocks
4−10
L
LenzeIOSystem.lib EN 1.7
ð Inputs
(Variable type: VAR_INPUT)
Variable name
Data type
Information/possible settings
bExecute
Bool
Execute write request
FALSE
ä TRUE Write request is executed
byNodeAdr
Byte
Device address: 1 − 63
byAnalogModuleNo
Byte
Slot number
·
The first analog module installed is assigned slot number 1.
·
A maximum of 16 analog modules may be plugged.
bEnableDiagnosticAlarm
Bool
Enable diagnostic alarm
TRUE Diagnostic alarm is enabled
bEnableAnalogInterrupt
Bool
Enable analog data transmission
TRUE Data transmission is enabled
byFunctionInput_CH1
...
byFunctionInput_CH2
Byte
Parameterise function
Default ±10V function parameter = 01
h
^ 6−6
bySampleRate_CH1
...
bySampleRate_CH2
Byte
Select number of conversions per second
0 15 conversions
1 30 conversions
2 60 conversions
3 123 conversions
4 168 conversions
5 202 conversions
6 3.7 conversions
7 7.5 conversions
byFunctionOutput_CH3
...
byFunctionOutput_CH4
Byte
Parameterise function
Default ±10V function code = 01
h
^ 6−6