Function library LenzeIOSystem.lib
Function blocks
4.10
L_IOParCompactModule − Parameterisation function
4−27
L
LenzeIOSystem.lib EN 1.7
(Variable type: VAR_INPUT)
ð Inputs
Variable name
Information/possible settings
Data type
wCobID_RxPDO1
Word
Set identifiers
Default values: Input setting = 0
RxPDO = I/O system receive identifiers
Identifiers can be given any setting with a specified value.
The identifiers are composed as follows if the input setting = 0.
Note!
The basic identifiers are outside the preassigned standard system bus range.
ID range: 384−831
This prevents IDs from coinciding with unassigned CAN objects on which the IO−lib is
based.
RxPDOX
Identifier =
Basic ID +
Node address
RxPDO1
837
835
2
byTransmissionType_RxPDO1
Byte
Transmission method
0 Event−controlled
1 Time−controlled
2 Event−controlled with superimposed cycle time
tCyceTime_TxPDO6
...
tCyceTime_TxPDO10
Time
Cycle time t = 0 − 65535 ms
wCobID_TxPDO1
Word
Set identifiers
Default values: Input setting = 0
TxPDO = I/O system receive identifiers
Identifiers can be given any setting with a specified value.
The identifiers are composed as follows if the input setting = 0.
The basic identifiers are outside the preassigned standard system bus range.
ID range: 384−831
This prevents IDs from coinciding with unassigned CAN objects on which the IO−lib is
based.
TxPDOX
Identifier =
Basic ID +
Node address
TxPDO1
838
836
2
byTransmissionType_TxPDO1
Byte
Transmission method
0 Event−controlled
1 Time−controlled
2 Event−controlled with superimposed cycle time
tInhibitTime_TxPDO6
...
tInhibitTime_TxPDO10
Time
Inhibit time t = 0 − 65535 ms
tCyceTime_TxPDO6
...
tCyceTime_TxPDO10
Time
Cycle time t = 0 − 65535 ms