Function library lenzeiosystem.lib, Function blocks – Lenze DDS Function library IOSystem User Manual
Page 31
Function library LenzeIOSystem.lib
Function blocks
4.5
L_IOParSSIModule − Parameterisation function
4−13
L
LenzeIOSystem.lib EN 1.7
Outputs
ð
(Variable type: VAR_OUTPUT)
Identifier
Data type
Value/meaning
nState
Integer
States
If a transmission error occurs during the parameterisation process, or the input data
are incorrect, the parameterisation process is aborted and an error number is
indicated at output nState.
Any errors are reset via an edge reversal at input bExecute or on
program restart.
0 Transmit command is executed.
The module is parameterised.
1 Transmit command sent
Processing in process
2001 Error occurred during bus transfer
2002 Transmit command timed out
2004 Access denied
Wrong target system: Subindex does not exist
2005 Access denied
Wrong target system: Index does not exist
2013 Access denied
Wrong target system: Invalid value range
2111 Access denied
Wrong target system: More than 4 digits specified after
comma, or no fixed−comma−format index
2117 Communication channel does not exist
Set byCom channel
−10xx Incorrect value at function block input.
XX := Number of faulty input (counting direction down),
parameterisation impossible.
Remedy: Change input value, restart data transmission