9300 servo plc, Appendix, 6 code table – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual
Page 125

9300 Servo PLC
Appendix
3.6
Code table
3−23
L
9300 Servo PLC EN 5.0
Code
Info
Possible settings
LCD
Code
Info
Selection
Lenze
LCD
C0061 Heatsink temp
g
Heatsink temperature
0
{1 °C}
100
C0063 Mot temp
g
Motor temperature
0
{1 °C}
200
C0064 Utilization
g
Controller load I x t during the last 180 seconds
·
C0064 >100 % trips OC5.
·
TRIP−RESET is only possible if C0064 < 95 %.
0
{1 %}
150
C0066 Motor load
g
I
2
× t−utilisation of the motor
0
{1 %}
250
C0067 Act trip
g
Current TRIP
("0" is displayed for FAIL−QSP, warning and message.)
C0070 Vp speed CTRL
à
Proportional gain of speed controller (V
pn
)
à
Dependent on C0086
·
If C0086 is changed, the value is reset to the assigned
Lenze setting.
0.0
{0.5}
255.0
C0071 Tn speed CTRL
à
Reset time of speed controller (T
nn
)
à
Dependent on C0086
·
If C0086 is changed, the value is reset to the assigned
Lenze setting.
1.0
{0.5 ms}
600.0
>512 ms = switched off
C0072 Td speed CTRL
0.0
Derivative gain of speed controller (T
dn
)
0.0
{0.1 ms}
32.0
C0075 Vp curr CTRL
à
Proportional gain of current controller (V
pi
)
à
Dependent on C0086
·
If C0086 is changed, the value is reset to the assigned
Lenze setting.
0.00
{0.01}
15.99
C0076 Tn curr CTRL
à
Reset time of current controller (T
ni
)
à
Dependent on C0086
·
If C0086 is changed, the value is reset to the assigned
Lenze setting.
0.5
{0.1 ms}
2000.0
2000 ms = switched off
C0077 Vp field CTRL
0.25
Proportional gain of field controller (V
pF
)
0.00
{0.01}
15.99
C0078 Tn field CTRL
15.0
Reset time of field controller (T
nF
)
1.0
{0.5 ms}
8000.0
8000 ms = switched off
[C0081] Mot power
à
Rated motor power according to nameplate
à
Dependent on C0086
·
If C0086 is changed, the value is reset to the assigned
Lenze setting.
·
Change sets C0086 = 0
0.01
{0.01 kW}
500.00
[C0084] Mot Rs
à
Stator resistance of the motor
à
Dependent on C0086
·
If C0086 is changed, the value is reset to the assigned
Lenze setting.
·
Change sets C0086 = 0.
0.00
{0.01
W}
100.00