C13118 | epl mn: link interruptions, C13122 | epl cn response error, C13124 | epl cn response error: monit. thresholds – Lenze E94AYCEP User Manual
Page 86: C13125 | epl mn: break after collisions, C13124, 11 parameter reference

11
Parameter reference
11.2
Parameters of the communication module for slot MXI1
87
Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13118
C13122
C13124
C13125
Parameter | Name:
C13118 | EPL MN: Link interruptions
Data type: UNSIGNED_32
Index: 11457 = 0x2CC1
EPL index: 0x1C03
The code displays the counter of the Managing Node for interrupted POWERLINK connections. Each event is
counted. Every single event is followed by an error response. A threshold value management is not implemented.
Setting range
(min. value | unit | max. value)
Lenze setting
0
4294967295 0
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13122 | EPL CN response error
Data type: UNSIGNED_32
Index: 11453 = 0x2CBD
EPL index: See subcodes
The subcodes of the code indicate Controlled Node-specific cumulative counters for missing PRes frames. The
behaviour corresponds to a node The behaviour corresponds to subcode 1 of the single error counters (
Each subcode corresponds to an EPL node with node ID = subcode number.
Setting range
(min. value | unit | max. value)
0
4294967295
Subcodes
Lenze setting
Info
EPL index
C13122/1
0
EPL CN response error
0x1C07.0x01
...
...
...
...
C13122/100
0
EPL CN response error
0x1C07.0x64
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13124 | EPL CN response error: monit. thresholds
Data type: UNSIGNED_32
Index: 11451 = 0x2CBB
EPL index: See subcodes
Setting range
(min. value | unit | max. value)
0
1000
Subcodes
Lenze setting
Info
EPL index
C13124/1
9
EPL CN response error: monit.
thresholds
0x1C09.0x01
...
...
...
...
C13124/100
9
EPL CN response error: monit.
thresholds
0x1C09.0x64
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13125 | EPL MN: Break after collisions
Data type: UNSIGNED_32
Index: 11450 = 0x2CBA
EPL index: 0x1C12
The code determines the number of EPL cycles for the duration of which the Managing Node interrupts the cycle
sequence after a POWERLINK collision has occurred.
Setting range
(min. value | unit | max. value)
Lenze setting
0
Cycles
100 1 cycles
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT