Epl: mn address assigned double [0x00c88283, Epl: internal error [0x00c88284, 0x00c88283 – Lenze E94AYCEP User Manual
Page 65: 0x00c88284, 10 error messages

Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17
66
10
Error messages
10.1
Error messages of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EPL: MN address assigned double [0x00c88283]
EPL: Internal error [0x00c88284]
Response (Lenze setting printed in bold)
Setting: not possible
No reaction System fault Fault Trouble Quick stop by trouble WarningLocked Warning Information
Cause
Remedy
The address setting of the Managing Node has been
assigned several times (node ID = ’240’).
This node is configured as Managing Node but does not
participate in the frame traffic due to double addressing.
Correct address setting.
Response (Lenze setting printed in bold)
Setting: not possible
No reaction System fault Fault Trouble Quick stop by trouble WarningLocked Warning Information
Cause
Remedy
Internal error.
Send communication module together with a
description of the fault to Lenze.