Commissioning
6.3
Settings and displays in the »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3
Settings and displays in the »Engineer«
Setting / display
Description
General
General information on the node type or the synchronisation of the
application
EPL address (project)
Setting of the POWERLINK address (node ID:
/
)
• If the address ’240’ (Managing Node) is set here, only "Application
synchronised via Powerlink" can be activated in the general settings.
• The "Managing Node node" supports max. 50 nodes.
Current EPL device address
Display of the current POWERLINK device address (
/
)
EPL host name
The DNS-compatible host name (
/
) has to be non-
ambiguous within the network domain.
The device name ...
• consists of max. 15 characters ([A ... Z], [a ... z], [0 ... 9], [ - ]);
• starts with a letter;
• ends with a letter or a digit.
EPL IP address
The IP address (
) is created from the POWERLINK address
(Node ID): 192.168.100.[
/
]
EPL MAC address
Display of the MAC address (
/
Open/close advanced
settings
Here, the POWERLINK communication can be reset.