beautypg.com

Troubleshooting: error messages and alarm, Table 5. error messages and next steps – Despatch LCC/LCD2-14-4 Oven Series with Protocol 3 User Manual

Page 50

background image

T

ROUBLESHOOTING

LCC/LCD2-14 Series Oven

Owner’s Manual

50

Version 1

Copyright © 2013 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.

7.

Troubleshooting: Error Messages and Alarm

Table 5 lists the more common error messages, possible problems and remedies.

Table 5. Error Messages and Next Steps.

Alarm Status

Possible Problem

Next Step

HI LIMIT LED ON

Problem with thermocouple

High Limit setpoint has been
exceeded

Once the problem has corrected,
press RESET.

DEV HOLD LED flashing

Oven temperature has not
entered (or dropped out of) the
Auto Hold band and the soak
timer has stopped

Program a slower ramp rate or, if
oven is not heating check heater
circuit.

Top PV displays OPEN

Control thermocouple is
disconnected or broken

Repair or replace the thermocouple.

HLPV displays OPEN

High Limit thermocouple is
disconnected or broken

Repair or replace the thermocouple.