List of parameters – 2N Helios IP Configuration Manual v2.8 User Manual
Page 35
35
List of Parameters
Switch enabled – enable/disable the switch globally. When disabled, the switch
cannot be activated by any of the available codes (including user switch codes),
by a call or quick dial button.
Switch mode – set the monostable/bistable mode for the switch. The switch is
switched off after a timeout in the monostable mode, and switched on with the
first activation and off with the next activation in the bistable mode.
Switch-on duration – set the switch-on time for a monostable switch. This
value is not applied in the bistable mode.
Time profile – assign the switch a time profile to enable switch-on. If the time
profile is inactive, the switch cannot be activated by a code, call or quick dial
button.
Controlled output – assign an electric output to the switch. Choose one of the
available intercom outputs: relay, power output, extender output. If you select
, the switch will not control any electric output but can control external
None
equipment via HTTP commands.
Output type – if you use the
Security Relay module, set the
2N
Helios IP
®
output type to
. In the
mode, the output works in the inverse
Security
Security
mode, i.e. remains closed and controls the
Security Relay module
2N
Helios IP
®
using a specific pulse sequence.
Note
Switch time profiles are available with the Gold or Enhanced Integration
licence only.