beautypg.com

Bryant 312AAV User Manual

Page 7

background image

per 3000 Btuh of the total input for all equipment within
the confined space and not less than the sum of the areas
of all vent connectors in the confined space. Equipment
clearances to the structure shall be at least 1 in. from the
sides and back and 6 in. from the front of the appliances.
See Table 2 and Fig. 8.

When ducts are used, they must be of the same cross sectional area

as the free area of the openings to which they connect. The

minimum dimension of ducts must not be less than 3 in.

III. AIR DUCTS

A. General Requirements
The duct system should be designed and sized according to

accepted national standards such as those published by: Air

Conditioning Contractors Association (ACCA), Sheet Metal and

Air Conditioning Contractors National Association (SMACNA) or

American Society of Heating, Refrigerating and Air Conditioning

Engineers (ASHRAE). Or consult The Air Systems Design Guide-
lines
reference tables available from your local distributor. The

duct system should be sized to handle the required system design

CFM at the design external static pressure.
When a furnace is installed so that the supply ducts carry air to

areas outside the space containing the furnace, the return air must

also be handled by a duct(s) sealed to the furnace casing and

terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used.

Seal supply- and return-duct connections to furnace with code

approved tape or duct sealer.

Flexible connections should be used between ductwork and

furnace to prevent transmission of vibration. Ductwork passing

through unconditioned space should be insulated to enhance

system performance. When air conditioning is used, a vapor

barrier is recommended.
Maintain a 1-in. clearance from combustible materials to supply air

ductwork for a distance of 36 in. horizontally from the furnace. See

NFPA 90B or local code for further requirements.

B. Ductwork Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and 10 ft

of main duct to the first branch take-off may require internal

acoustical lining. As an alternative, fibrous ductwork may be used

if constructed and installed in accordance with the latest edition of

SMACNA construction standard on fibrous glass ducts. Both

acoustical lining and fibrous ductwork shall comply with NFPA

90B as tested by UL Standard 181 for Class 1 Rigid air ducts.

C. Supply Air Connections

UPFLOW FURNACES
Connect supply-air duct to 3/4-in. flange on furnace supply-air

outlet. Bend flange upward to 90° with wide duct pliers. The

supply-air duct attachment must ONLY be connected to furnace

supply-/outlet-air duct flanges or air conditioning coil casing

(when used). DO NOT cut main furnace casing to attach supply

side air duct, humidifier, or other accessories. All accessories

MUST be connected external to furnace main casing. Supply air

opening duct flanges must be modified per Fig. 14.

SUPPLY

AIR

6″ MIN

(FRONT)

RETURN AIR

VENT THROUGH ROOF

1 SQ IN.

PER 1000

BTUH* IN DOOR

OR WALL

12″ MAX

1 SQ IN.

PER 1000

BTUH* IN DOOR

OR WALL

12″ MAX

INTERIOR

HEATED

SPACE

* Minimum opening size is 100 sq in. with

minimum dimensions of 3 in.

Minimum of 3 in. when type-B1 vent is used.

UNCONFINED

SPACE

CONFINED SPACE

A89012

Fig. 7–Confined Space: Air for Combustion and Ventilation

from an Unconfined Indoor Space

1 SQ IN.

PER

4000

BTUH*

DUCTS

TO

OUTDOORS

1 SQ IN.

PER 4000

BTUH*

SUPPLY

AIR

VENT

THROUGH

ROOF

D

B

A

C

E

1 SQ IN.

PER 4000

BTUH*

DUCT

TO

OUTDOORS

RETURN AIR

1 SQ IN.

PER 2000

BTUH*

1 SQ IN.

PER 2000

BTUH*

DUCTS

TO

OUTDOORS

12″ MAX

12″ MAX

12″ MAX

Use any of the following

combinations of openings:

A & B C & D D & E F & G

NOTE:

*

Minimum dimensions of 3 in.

CONFINED SPACE

12″

MAX

12″

MAX

OUTDOORS

1 SQ IN.

PER

4000

BTUH*

F

G

A89013

Fig. 8–Confined Space: Air for Combustion and Ventilation

from Outdoors

—7—