beautypg.com

Bryant 312AAV User Manual

Page 20

background image

furnace control CPU will hold the blower motor BLWM at

HI HEAT speed during the selected blower-OFF delay

period before reverting to continuous-blower speed.

When the thermostat

″calls for low-cooling″, the blower

motor BLWM will switch to operate at low-cool speed

(same speed as LO-HEAT). When the thermostat is satis-

fied, the blower motor BLWM will operate an additional 90

seconds on low-cool speed before reverting back to

continuous-blower speed.

When the thermostat

″calls for high-cooling″, the blower

motor BLWM will operate at COOL speed. When the

thermostat is satisfied, the blower motor BLWM will

operate an additional 90 seconds on COOL speed before

reverting back to continuous-blower speed.

When the R-to-G circuit is opened, the blower motor

BLWM will continue operating for an additional 5 seconds,

if no other function requires blower motor BLWM opera-

tion.

Continuous-Blower Speed Selection from Thermostat-

To select different continuous-blower speeds from the room

thermostat, momentarily turn the FAN switch or push-

button on the room thermostat to OFF (AUTO) for 1-3

seconds after the blower motor BLWM is operating. The

furnace control CPU will shift the continuous-blower speed

from the factory setting of LO-HEAT to HI-HEAT speed.

Momentarily turning the FAN switch to OFF (AUTO) again

at the thermostat will shift the continuous-blower speed

from HI-HEAT to COOL. Repeating the procedure will

shift the continuous-blower speed from COOL to LO-

HEAT speed. The selection can be changed as many times

as desired and is stored in the memory to be automatically

used following a power interruption.

6. Heat Pump

(See Fig. 26, 27, 28, and 29 for thermostat connections)

When installed with a heat pump, the furnace control

automatically changes the timing sequence to avoid long

blower off times during demand defrost cycles. When the

R-to-W/W1-and-Y1 or R-to-W/W1-and-Y1-and-G circuits

are energized the furnace control CPU will switch to or turn

on the blower motor BLWM at low-cool speed (same speed

as LO-HEAT), and begin a low-heat cycle. The blower

motor BLWM will remain on until the end of the prepurge

period, then shut off for 24 seconds, then come back on at

LO-HEAT speed. When the W/W1 input signal disappears,

the furnace control begins a normal inducer post-purge

period and the blower remains running at LO-HEAT speed.

If the R-to-W/W1-and-Y1-and-G signals disappear at the

same time, the blower motor BLWM will remain on for the

selected blower-OFF delay period. If the R-to-W/W1-

and-Y1 signals disappear, leaving the G signal, the blower

motor BLWM will remain on for the selected blower-OFF

delay period then switch to continuous-blower speed.

When the R-to-W/W1-and-Y/Y2, R-to-W/W1-and-Y/Y2-

and-G, R-to-W/W1-and-Y1-and-Y/Y2, or R-to-W/W1-and-

Y1-and-Y/Y2-and-G circuits are energized the furnace

control CPU will switch to or turn on the blower motor

BLWM at COOL speed, and begin a high-heat cycle. The

blower motor BLWM will remain on until the end of the

prepurge period, then shut off for 24 seconds then come

back on at HI-HEAT speed. When the W/W1 input signal

disappears, the furnace control begins a normal inducer

post-purge period and the blower switches to COOL speed

after a 3-second delay. If the R-to-W/W1-and-Y/Y2-and-G

or R-to-W/W1-and-Y1-and-Y/Y2-and-G signals disappear

at the same time, the blower motor BLWM will remain on

for the selected blower-OFF delay period. If the R-to-

W/W1-and-Y/Y2 or R-to-W/W1-and-Y1-and-Y/Y2 signals

disappear, leaving the G signal, the blower motor BLWM

will remain on for the selected blower-OFF delay period,

then switch to continuous-blower speed.

1. Heat pump MUST have a high pressure switch for dual fuel

applications.

2. Refer to outdoor equipment Installation Instructions for

additional information and setup procedure.

3. Select the “ZONE” position on the two-speed heat pump

control.

4. Outdoor Air Temperature Sensor must be attached in all

dual fuel applications.

5. Dip switch No. 1 on Thermidistat should be set in OFF

position for air conditioner installations. This is factory

default.

6. Dip switch No. 1 on Thermidistat should be set inON

position for heat pump installations.

7. Dip switch No. 2 on Thermidistat should be set in OFF

position for single-speed compressor operation. This is

factory default.

8. Dip switch No. 2 on Thermidistat should be set in ON

position for two-speed compressor operation.

9. Configuration Option No. 10 “Dual Fuel Selection” must be

turnedON in all dual fuel applications.

10. NO connection should be made to the furnace HUM

terminal when using a Thermidistat.

11. Optional connection. If wire is connected, dip switch No. 1

on furnace control should be set in ON position to allow

Thermidistat/Thermostat to control furnace staging.

12. Optional connection. If wire is connected, ACRDJ jumper

on furnace control shouild be removed to allow

Thermidistat/Thermostat to control outdoor unit staging.

13. Furnace must control its own high-stage heating operation

via furnace control algorithm. This is factory default.

14. The RVS Sensing terminal “L” should not be connected.

This is internally used to sense defrost operation.

15. DO NOT SELECT the “FURNACE INTERFACE” or

“BALANCE POINT” option on the two-speed heat pump

control board. This is controlled internally by the

Thermidistat/Dual Fuel Thermostat.

16. Dip switch D on Dual Fuel Thermostat should be set in

OFF position for single-speed compressor operation. This

is factory default.

17. Dip switch D on Dual Fuel Thermostat should be set in ON

position for two-speed compressor operation.

III. START-UP PROCEDURES

1. Purge Gas Lines:After all connections have been made,

purge the lines and check for leaks.

WARNING: Never purge a line into a combustion

chamber. Never use matches, candles, flame, or other

sources of ignition for the purpose of checking leakage.

Use a soap-and-water solution to check for leakage.

Failure to follow this warning can cause fire, explosion,

personal injury, or death.

2. Component Self-Test:The furnace control allows all com-

ponents, except the gas valve, to be run for short period of

time. This feature helps diagnose a system problem in case

of a component failure. To begin component test procedure,

short (jumper) the C

OM

-24v terminal on control and the

TEST/TWIN 3/16-inch quick-connect terminal on control

(behind the C

OM

-24v terminal) for approximately 2 sec.

(See Fig. 22.)

—20—