Bryant 312AAV User Manual
Page 12
![background image](/manuals/54569/12/background.png)
WARNING: Use proper length of pipe to avoid stress on
gas control manifold. Failure to follow this warning could
result in a gas leak resulting in fire, explosion, personal
injury, or death.
Install a sediment trap in riser leading to furnace. Trap can be
installed by connecting a tee to riser leading to furnace so
straight-through section of tee is vertical. Then connect a capped
nipple into lower end of tee. Capped nipple should extend below
level of gas controls. Place a ground joint union between gas
control manifold and manual gas shutoff valve. (See Fig. 18.)
Piping should be pressure tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), turn off electric shutoff switch located on the
gas valve before the test. It is recommended that the ground joint
union be loosened before pressure testing.
After all connections have been made, purge the lines and check
for gas leakage with regulated gas supply pressure.
An accessible manual shutoff valve MUST be installed upstream
of furnace gas controls and within 6 ft of furnace. A 1/8-in. NPT
plugged tapping, accessible for test gage connection, MUST be
installed immediately upstream of gas supply connection to
furnace and downstream of manual shutoff valve.
NOTE: The gas valve inlet pressure tap connection is suitable to
use as test gage connection providing test pressure DOES NOT
exceed maximum 0.5 psig (14-in. wc) stated on gas valve. (See
Fig. 33.) Piping should be pressure tested in accordance with
NFGC, local and national plumbing and gas codes before furnace
is attached. In Canada, refer to current edition of NSCNGPIC.
VIII. ELECTRICAL CONNECTIONS
See Fig. 21 for field wiring diagram showing typical field 115-v
wiring.Check all factory and field electrical connections for
tightness.
WARNING: Blower access panel door switch opens
115-v power to control. No component operation can
occur. Do not bypass or close switch with panel removed.
Failure to follow this warning could result in personal
injury or death.
CAUTION: Furnace control must be grounded for
proper operation or control will lock out. Control is
grounded through green wire routed to gas valve and
burner box screw.
A. 115–v Wiring
Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on unit
rating plate. Also, check to be sure that service provided by utility
is sufficient to handle load imposed by this equipment. Refer to
rating plate or Table 6 for equipment electrical specifications.
Make all electrical connections in accordance with National
Electrical Code (NEC) ANSI/NFPA 70-1999 and any local codes
or ordinances that might apply. For Canadian installations, all
electrical connections must be made in accordance with Canadian
Electrical Code CSA C22.1 or authorities having jurisdiction.
CAUTION: Do not connect aluminum wire between
disconnect switch and furnace. Use only copper wire.
CAUTION:
Use a separate, fused branch electrical circuit containing a properly
sized fuse or circuit breaker for this furnace. See Table 6 for wire
size and fuse specifications. A disconnecting means must be
located within sight from and readily accessible to furnace.
NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control LED status indicator light will flash
rapidly and furnace will NOT operate.
TABLE 4–FILTER INFORMATION (IN.)
FURNACE
CASING WIDTH
FILTER SIZE
FILTER
TYPE
Side Return
Bottom Return
17–1/2
(1) 16 x 25 x 1† (1) 16 x 25 x 1† Cleanable
† Factory provided with the furnace.
TABLE 5–MAXIMUM CAPACITY OF PIPE*
NOMINAL
IRON
PIPE
SIZE
(IN.)
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10
20
30
40
50
1/2
0.622
175
120
97
82
73
3/4
0.824
360
250
200
170
151
1
1.049
680
465
375
320
285
1–1/4
1.380
1400
950
770
660
580
1–1/2
1.610
2100
1460
1180
990
900
* Cubic tf if gas per hr for gas pressure of 0.5 psig (14–in wc) or less, and a
pressure drop of 0.5–in wc (based on a 0.60 specific gravity gas).
Ref: Table 10–2 NFGC.
Fig.16–Horizontal Installation on Blocks
A00344
—12—