beautypg.com

Bryant 312AAV User Manual

Page 27

background image

Place LHT in ON position. Jumper R to W/W1 and W2 to

check high-gas-heat temperature rise. To check low-gas-

heat temperature rise, remove jumper to W2. Determine air

temperature rise for both high and low fire. Do not exceed

temperature rise ranges specified on unit rating plate for

high-and low-fire.

The furnace must operate within the temperature rise ranges

specified on the furnace rating plate. Determine the air

temperature as follows:
a. Place thermometers in return and supply ducts as close to

furnace as possible. Be sure thermometers do not see
heat exchangers so that radiant heat does not affect
readings. This practice is particularly important with
straight-run ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine
air temperature rise.

NOTE: If the temperature rise is outside this range, first check:

(1.) Gas input for low-and high-fire opeation.
(2.) Derate for altitude if applicable.
(3.) Return and supply ducts for excessive restrictions

causing static pressures greater than 0.50–in. wc.

c. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise. Fro
high fire, speed selection can be med-high, med
(5–speed blowers only), or med-low (factory setting).
For low fire, speed selection can be low (factory setting),
med-low, or med (5–speed blowers only).

WARNING: Disconnect 115-v electrical power before

changing speed tap. Failure to follow this warning could

result in personal injury.

d. To change motor speed selection for high heat, remove

blower motor lead from control HI-HEAT terminal. (See
Fig. 22 and 23.) Select desired blower motor speed lead
from 1 of the other terminals and relocate it to the
HI-HEAT terminal. (See Table 11 for lead color identi-
fication). Reconnect original lead to SPARE terminal.
Follow this procedure for proper selection of COOL and
LO-HEAT speed selection.

CAUTION: Recheck temperature rise. It must be within

limits specified on the rating plate. Recommended opera-

tion is at the midpoint of rise range or above.

8. Set thermostat heat anticipator.

a. When using a nonelectric thermostat, the thermostat

heat-anticipation must be set to match the amp draw of
the electrical components in the R-W/W1 circuit. Accu-

rate amp draw readings can be obtained at the wires
normally connected to thermostat subbase terminals, R
and W/W1.
Fig. 16 illustrates an easy method of obtaining actual
amp draw. The amp reading should be taken after blower
motot has started and furnace is operating in low-heat.
To operate furnace in low-heat, first move LHT to ON
position, then connect ammeter wires as shown in Fig.
37. The thermostat anticipator should NOT be in th
circuit while measuring current. If thermostat has no
subbase, the thermostat must be disconnected from R
and W/W1 wires during current measurement. Return
LHT to OFF after completing the reading. See thermo-
stat manufacturer’s instructions for adjusting heat-
anticipator.

b. When using an elctronic thermostat, set cycle rate for 3

cycles per hr.

V. CHECK SAFETY CONTROLS
The flame sensor, gas valve, and pressure switch were all checked

in the Start-up procedure section as part of normal operation.

1. Check Main Limit Switches

This control shuts off combustion control system and energizes

air-circulating blower motor, if furnace overheats.
Recommended method of checking this limit control is to gradu-

ally block off return air after furnace has been operating for a

period of at least 5 minutes. As soon as limit control has shut off

burners, return-air opening should be unblocked to permit normal

air circulation. By using this method to check limit control, it can

be established that limit is functioning properly and will operate if

there is a restricted return-air supply or motor failure. If limit

control does not function during this test, cause must be deter-

mined and corrected.

TABLE 11–SPEED SELECTION

COLOR

SPEED

AS SHIPPED

White

Common

BLW

Black

High

COOL

Yellow

Med-High

SPARE

Orange†

Med

SPARE

Blue

Med-Low

HI-HEAT

Red

Low*

LO HEAT

* Continuous-blower speed-as shipped default
† Available on 5–speed blowers only.

TABLE 12–GAS RATE (CU FT/HR)

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

1

Cu Ft

2

Cu Ft

5

Cu Ft

1

Cu Ft

2

Cu Ft

5

Cu Ft

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

15

240

480

1200

55

65

131

327

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

1000

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21

171

343

857

62

58

116

290

22

164

327

818

64

56

112

281

23

157

313

783

66

54

109

273

24

150

300

750

68

53

106

265

25

144

288

720

70

51

103

257

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

30

120

240

600

80

45

90

225

31

116

232

581

82

44

88

220

32

113

225

563

84

43

86

214

33

109

218

545

86

42

84

209

34

106

212

529

88

41

82

205

35

103

206

514

90

40

80

200

36

100

200

500

92

39

78

196

37

97

195

486

94

38

76

192

38

95

189

474

96

38

75

188

39

92

185

462

98

37

74

184

40

90

180

450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

106

34

68

170

44

82

164

409

108

33

67

167

45

80

160

400

110

33

65

164

46

78

157

391

112

32

64

161

47

76

153

383

116

31

62

155

48

75

150

375

120

30

60

150

49

73

147

367

—27—