beautypg.com

Bryant 312AAV User Manual

Page 26

background image

d. Check and verify orifice size in furnace. NEVER AS-

SUME THE ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.

e. Turn off all other gas appliances and pilots.
f. Move setup switch LHT to ON position. (See Fig. 22.)

This keeps furnace locked in low-heat operation.

g. Jumper R to W/W1.
h. Let furnace run for 3 minutes in low-heat operation.
i. Measure time (in sec) for gas meter to complete 1

revolution. Note reading.

j. Refer to Table 11 for cubic ft of gas per hr.

k. Multiply gas rtate cu ft/hr by heating value (Btu/cu ft).
l. Move setup switch LHT to OFF position and jumper R

and W2 thermostat connections. (See Fig. 22.) This keeps
furnace locked in high-heat operation. Repeat items h
through k for high-heat operation.

EXAMPLE: (High–heat operation at 0-2000 ft altitude)

Furnace input from rating plate is 88,000 Btuh.

Btu heating input = Btu/cu ft X cu ft/hr

Heating value of gas = 1050 Btu/cu ft

Time for 1 revolution of 2-cu ft dial = 87 sec

Gas rate = 83 cu ft/hr (from Table 11)

Btu heating input = 83 X 1050 = 87,150 Btuh. In this

example, the orifice size and manifold pressure adjustment

is within ±2 percent of the furnace input rate.

NOTE: Measured gas inputs (high-heat and low-heat) must be

within ± 2 percent of that stated on furnace rating plate when

installed at sea level or derated per that stated above when installed

at higher altitudes.

m. Remove jumper across R, W/W1, and W2 thermostat

connections to terminate call for heat.

7. Set temperature rise.

Fig. 32–Redundant Automatic Gas Control Valve

A00158

ON/OFF

SWITCH

INLET

PRESSURE

TAP

ON

O

F

F

MANIFOLD

PRESSURE

TAP

LOW-FIRE

ADJUSTMENT

ALLEN SCREW

(UNDER CAP)

HIGH-FIRE

ADJUSTMENT

ALLEN SCREW

(UNDER CAP)

Fig. 33–Orifice Hole

A93059

BURNER

ORIFICE

CAUTION: DO NOT redrill orifices. Improper drilling

(burrs, out-of-round holes, etc.) can cause excessive

burner noise and misdirection of burner flames. This can

result in flame impingement of heat exchangers, causing

failures.

Fig. 34-Burner Flame

A89020

;;

;;

BURNER FLAME

BURNER

MANIFOLD

TABLE 10–ALTITUDE DERATE MULTIPLIER FOR U.S.A.

ALTITUDE

(FT)

PERCENT

OF DERATE

DERATE MULTIPLIER

FACTOR FOR U.S.A.*

0–2000

0

1.00

2001–3000

8–12

0.90

3001–4000

12–16

0.86

4001–5000

16–20

0.82

5001–6000

20–24

0.78

6001–7000

24–28

0.74

7001–8000

28–32

0.70

8001–9000

32–36

0.66

9001–10,000

36–40

0.62

* Derate multiplier factor is based on midpoint altitude for altitude range.

EXAMPLE:

88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT.

Derate

Furnace Input Rate

Furnace Input Rate

X

Multiplier

=

at Installation

at Sea Level

Factor

Altitude

88,000

X

0.82

=

72,160

—26—