beautypg.com

Sioux Chief Fire-Rated OxBox Outlet Box User Manual

Fire-rated oxbox outlet box

background image

FIRE-RATED OXBOX OUTLET BOX

DESIGN SPECIFICATION

1 WALL CONSTRUCTION

a Wood or metal stud construction, max 100 in.² of penetrations per 100 ft² of wall
b Single-layer

5 8

" gypsum construction with 1-hour fire rating

c Double-layer

5 8

" gypsum construction with 2-hour fire rating

d Boxes cannot be installed back to back

2 PIPE/BOX SUPPORT

a Each outlet box must be installed in a separate stud bay and attached to the stud, as

shown below in “over-stud” or “separate stud bay” installation examples. Fire rating

does not apply to installations of two or more boxes in the same stud bay.

b Supplied support bar to be installed through at least one box’s slotted opening

c Supply lines to be installed using ordinary methods

d Drain line to be supported using ordinary methods

3 PIPE MATERIAL

a 2" or larger metallic, PVC, or ABS DWV pipe

b Metallic or plastic water supply pipe

4 FIRESTOP DEVICE

a Sioux Chief fire-rated OxBox frame and frame extension are constructed using

fire-rated resin. Boxes have 4" × 4" intumescent adhesive pads factory installed on

the back of boxes.

NOTE: Gaps up to ½" around box can be sealed with drywall plaster. Larger gaps require firestop sealant applied

to opening spanning entire drywall depth

"over stud" installation

"separate stud bay" installation

Sioux Chief Manufacturing Company | P: 1.800.821.3944 | F: 1.800.758.5950 | www.siouxchief.com

4-14

1

2

3

4

Fire-rated ABS

Intumescent pads

THE FIRE-RATED OX BOX IS CERTIFIED BY INTERTEK/WARNOCK
HERSEY TO THE FOLLOWING FIRE RATING STANDARDS:

ASTM E-814

2 hours (F), 1½ hours (T)

for 2-hour design

1 hour (F), 31 mins (T)

for 1-hour design

ASTM E119

CAN/ULC S115

2 hours (F), 1½ hours (T)

for 2-hour design

1 hour (F), 31 mins (T)

for 1-hour design

UL 1479