NOVUS Web Server – WS10 User Manual
Page 23

Web Server – WS10
NOVUS AUTOMATION
23/33
Section
Sub-Section
Parameter
Values
Description
LinkType
ETH or PPP
Type of connection.
ETH: Ethernet.
PPP: PPP connection configured at the PPP.CFG file.
SMTPServer
IP address
IP address of the SMTP server. Must be accessible through the
specified connection. If a DNS configuration exists, a domain name can
be specified in substitution of the IP address.
SMTPPort
SMTP Port
Port used to connect the SMTP Server. If this parameter is not set the
Port 25 will be assumend as standard.
Login
User name
Login name to the SMTP server. Omit this parameter line if the server
doesn’t require authentication.
Pass
User password
Login password to the SMTP server. Omit this parameter line if the
server doesn’t require authentication.
FromAddress
E-mail address
Return address for the e-mail message. Set to a valid e-mail address to
allow reception of error messages on delivery failures.
Name
Name
Name of the message sender.
General
TimeZone
Time zone value
Time zone where the WS10 is installed. Examples: -3, +2:30.
DestList
List of e-mail
addresses
List of e-mail addresses to whom this message will be sent. One
address per line.
Subject
Line of text
Subject line of the message. May contain references to device/tag,
enclosed by 2 % characters.
MessageBody
Lines of text or HTML
Multiple lines of message body. May contain references to device/tag,
enclosed by 2 % characters. If HTML code is detected, the email is sent
in HTML format. The last line must contain a single period character to
define the end of message body.
Attachment
Device/Tag
If the message should contain the content of the data logger file, include
this sub-section and one of the references to the log registers below:
_INTERNAL_/_LOG to send and don’t erase the log file
_INTERNAL_/_LOG_E to send and erase the log file
Usage of LOG_E is unsafe.
Interval
0 to 65535
Interval in minutes of the periodic transmission of this message.
Program 0 to disable periodic transmission.
Scheduler
TimeFilter
0 to 65535
Minimum interval in minutes between consecutive transmissions of this
message when triggered by registers. Used to limit the frequency of
exception email messages.
Nome do e-mail
TriggerList
Device/Tag list
List of registers that can trigger the transmission of this message. When
any of the listed registers change from zero to non-zero value, the
message is triggered. If the register is of the memory type, the WS10
write 0 to it after the message is sent.
Multiple e-mail messages can be defined, one at each section as the one described above.
Depending on the type of connection to the SMTP server, a long time should be required to transfer the message. This is more critical with PPP
(modem) connection, where connection negotiation may take one minute or more. The message is constructed by the WS10 after the connection to
the SMTP server is established, and all dynamic information will be acquired at this moment. Sometimes the condition that triggered the email will
be finished when the message is finally posted, and this possibility should be considered on the design of the supervisory system.