beautypg.com

12 in – Red Lion P16 User Manual

Page 8

background image

8

SETPOINT VALUE (SP1) *

SETPOINT VALUE (SP2) *



to







2

2



% OUTPUT POWER *

1

to

1



to



Typically, the controller is operating with the Setpoint value in the bottom

display. There is no annunciator nor parameter indication for Setpoint in the

Display Loop. The parameter name alternates with the setpoint value in the

Hidden Loop. The Setpoint value can be changed, activated and stored by

pressing the arrow keys. This is the only parameter that can be configured as

read only in the Display Loop, but read/write in the Hidden Loop. It is possible

to store a second Setpoint value that can be selected in the Hidden Loop, by the

F1 key or the user input. Both Setpoint values are limited by the Setpoint Low

and High Limits in Input Module

1-IN

.

The % Output Power is shown with the %PW annunciator. The parameter

name alternates with the % Output Power value in the Hidden Loop. While the

controller is in Automatic Mode, this value is read only. When the controller is

placed in Manual Mode, the value can be changed, activated and stored by

pressing the arrow keys. For more details on % Output Power, see Control

Mode Explanations.

12

In

INTEGRAL TIME

to



seconds

Integral action shifts the center point position of the proportional band to

eliminate error in the steady state. The higher the integral time, the slower the

response. The optimal integral time is best determined during PID Tuning. If

time is set to zero, the previous Integral output power value is maintained.

Offset Power can be used to provide Manual Reset.





DERIVATIVE TIME

to



seconds per repeat

Derivative time helps to stabilize the response, but too high of a derivative

time, coupled with noisy signal processes, may cause the output to fluctuate too

greatly, yielding poor control. Setting the time to zero disables derivative action.

ALARM 1 VALUE



to



On models with alarms, the value for Alarm 1 can be entered here. The value

is either absolute (absolute alarm types) or relative to the Setpoint value

(deviation and band alarm types.) When Alarm 1 is programmed for  or
n

, this parameter is not available. For more details on alarms, see Alarm

Module

4-AL

.



F

OUTPUT POWER OFFSET

When the Integral Time is set to zero and the controller is in the Automatic

Mode, this parameter will appear after % Output Power. It is also shown with

the %PW annunciator illuminated. The power offset is used to shift the

proportional band to compensate for errors in the steady state. If Integral Action

is later invoked, the controller will re-calculate the internal integral value to

provide “bumpless” transfer and Output Power Offset will not be necessary.





PROPORTIONAL BAND



to



(% of full input range)

The proportional band should be set to obtain the best response to a process

disturbance while minimizing overshoot. A proportional band of 0.0% forces

the controller into On/Off Control with its characteristic cycling at Setpoint. For

more information, see Control Mode and PID Tuning Explanations.

* Alternating indication only used in the Hidden Loop.

ALARM 2 VALUE



to



On models with alarms, the value for Alarm 2 can be entered here. The value

is either absolute (absolute alarm types) or relative to the Setpoint value

(deviation and band alarm types.) When Alarm 2 is programmed for  or
n

, this parameter is not available. For more details on alarms, see the Alarm

Module .

The values shown for the displays are the factory settings.

T16

P16



1

T16

P16



2

T16

P16





T16

P16

1

to

1

This manual is related to the following products: