7.4 module 4 - A

lArm

p

ArAmeterS

(

4-AL

) (o

ptionAl

)

ACt1

rSt1

Lit1

Stb1

AL-1

ACt2

Lit2

ALARM 1

ACTION

ALARM 1

ANNUNCIATOR

ALARM 1

RESET

ANNUNCIATOR

ALARM 2

ALARM 2

ACTION

4-AL

CNFP

AHYS

HYSTERESIS

ALARM 1 & 2

ALARM 1

VALUE

RESET

ALARM 2

STANDBY

ALARM 2

rSt2

stb2

MODE

STANDBY

ALARM 1

MODE

AL-2

ALARM 2

VALUE

A

A

PARAMETER MENU

OFF

ON

AL + ½Hys

AL

AL - ½Hys

OFF

Absolute High Acting (Balanced Hys)

Hys

TRIGGER POINTS

ALARM

STATE

ALARM

STATE

OFF

ON

Hys

SP + AL

SP

OFF

TRIGGER POINTS

Deviation High Acting (AL > 0)

ALARM

STATE

Hys

SP - AL

SP

SP + AL

Hys

TRIGGER POINTS

ON

OFF

OFF

ON

ON

Band Inside Acting

OFF

ON

AL + ½Hys

AL

AL - ½Hys

OFF

Absolute Low Acting (Balanced Hys)

TRIGGER POINTS

Hys

ALARM

STATE

ALARM

STATE

OFF

ON

Hys

SP - AL

SP

OFF

TRIGGER POINTS

Deviation Low Acting (AL > 0)

ALARM

STATE

OFF

ON

Hys

AL

AL - Hys

OFF

TRIGGER POINTS

Absolute High Acting (Unbalanced Hys)

ALARM

STATE

OFF

ON

Hys

AL + Hys

AL

OFF

TRIGGER POINTS

Absolute Low Acting (Unbalanced Hys)

ALARM

STATE

ON

OFF

Hys

SP + (-AL)

SP

ON

TRIGGER POINTS

Deviation High Acting (AL< 0)

ALARM

STATE

ON

Hys

SP - AL

SP

OFF

SP + AL

ON

Hys

OFF

OFF

TRIGGER POINTS

Band Outside Acting

ALARM ACTION FIGURES

Note: Hys in the above figures refers to the Alarm Hysteresis.

AVAILABLE ALARM ACTIONS



None

No action, the remaining Alarm

parameters are not available.

I

Absolute High

(balanced hysteresis)

The alarm energizes when the Process

Value exceeds the alarm value + 1/2

the hysteresis value.



Absolute Low

(balanced hysteresis)

The alarm energizes when the Process

Value falls below the alarm value -1/2

the hysteresis value.

I

Absolute High

(unbalanced hysteresis)

The alarm energizes when the Process

Value exceeds the alarm value.



Absolute Low

(unbalanced hysteresis)

The alarm energizes when the Process

Value falls below the alarm value.

I

Deviation High

Alarm 1 and 2 value tracks the

Setpoint value



Deviation Low

Alarm 1 and 2 value tracks the

Setpoint value

I

Band Acting

(inside)

Alarm 1 and 2 value tracks the

Setpoint value



Band Acting

(outside)

Alarm 1 and 2 value tracks the

Setpoint value



Heat (A1 Analog

models only)

If heating is selected, the remaining

Alarm 1 parameters are not available.



Cool

(A2 only)

If cooling is selected, the remaining

Alarm 2 parameters are not available.