Page 19: Fs ), Actory, Ervice, Perations, Parameter menu

background image

19

The controller is fully calibrated from the factory. Recalibration is

recommended every two years by qualified technicians using appropriate

equipment. Calibration may be performed by using the front panel or with the

TP16KIT. The front panel method is explained below. (Refer to the TP16KIT

bulletin for calibration instructions using TP16KIT cable and software.)

Calibration may be aborted by disconnecting power to the controller before

exiting Factory Service Module F. In this case, the existing calibration

settings remain in effect.

Note: Allow the controller to warm up for 30 minutes minimum and follow

the manufacturer’s warm-up recommendations for the calibration source or

measuring device.

Cold Junction (T16)

Cold Junction calibration requires a thermocouple of known accuracy of

types T, E, J, K, C or N (connected to terminals 8 and 9) and a calibrated

external reference thermocouple probe measuring in °C with resolution to

tenths. The two probes should be brought in contact with each other or in some

way held at the same temperature. They should be shielded from air movement

and allowed sufficient time to equalize in temperature. (As an alternative, the

T16 thermocouple may be placed in a calibration bath of known temperature.)

If performing the millivolt calibration prior, verify that the correct input type is

configured in Input Module 1I before performing the following procedure.

(After the millivolt calibration the controller will default to type J.) If using RTD

only, the cold junction calibration need not be performed.

RTD Resistance (T16)

RTD calibration requires a precision 277.0 ohm resistor with an accuracy of

0.1 Ω (or better). Connect a jumper between terminals 9 and 10 with a 0 ohm

jumper between 9 and 8 at 1 and the 277.0 ohm resistor between 9 and 8 at
2

. If using thermocouple only, the RTD calibration need not be performed.

Input Calibration (P16)

Process calibration requires a precision signal source with an accuracy of

0.03% (or better) that is capable of generating 10.0 V connected to terminals 8

(COMM) and 9 (+10V) and 20.00 mA connected to terminals 8 (COMM) and

10 (20mA). The current calibration can be skipped by pressing A at the not

applicable prompts if using the controller for process voltage only.

CALIBRATION

7.5 module 9 F

ACtory

S

erviCe

o

perAtionS

(9-FS)

CodE

FACTORY

SERVICE CODE

9-FS CNFP

A

Millivolt Calibration (T16)

Millivolt calibration requires a precision voltage source with an accuracy of

0.03% (or better) connected to terminals 8 (comm.) and 9 (+). When calibrating

the input, the millivolt calibration must be performed first, then the Cold Junction

or RTD Resistance.





PARAMETER MENU

PROMPT

APPLY

FRONT PANEL ACTION



Press J until



, press A.



Press A.



Press A.



Press B for



, press A.

1

0.0 ohm

After 5 seconds (minimum), press A.

2

277.0 ohm After 5 seconds (minimum), press A.

PROMPT

APPLY

FRONT PANEL ACTION



Press J until



, press A.



Press B for



, press A.

1

0.0 ohm

After 5 seconds (minimum), press A.

2

2.5 V

After 5 seconds (minimum), press A.



5.0 V

After 5 seconds (minimum), press A.



7.5 V

After 5 seconds (minimum), press A.



10.0 V

After 5 seconds (minimum), press A.



0.0 mA

After 5 seconds (minimum), press A.



20.0 mA

After 5 seconds (minimum), press A.

PROMPT

APPLY

FRONT PANEL ACTION



Press J until



, press A.



Press B for



, press A.

1

0.0 ohm

After 5 seconds (minimum), press A.

2

14.0 mV

After 5 seconds (minimum), press A.



28.0 mV

After 5 seconds (minimum), press A.



42.0 mV

After 5 seconds (minimum), press A.



56.0 mV

After 5 seconds (minimum), press A.

PROMPT

COMPARE

FRONT PANEL ACTION



Press J until



, press A.



Press A.



Press B for



, press A.

Top display to

external

reference

Press B or J to adjust the

bottom display until the top

process display matches the

external reference then press A.