rogrAmming

: C

onFigurAtion

l

oop

2-OP

1-IN

3-LC

4-AL

5-O2

9-FS

no

CNFP

LOOP

HIDDEN

DISPLAY

LOOP

PARAMETERS

INPUT

MODULE

MODULE

OUTPUT

PARAMETERS

LOCKOUT

PARAMETERS

MODULE

COOLING

PARAMETERS

MODULE

FACTORY

SERVICE

MODULE

ALARM

PARAMETERS

MODULE

CONFIGURATION LOOP

FRONT DISPLAY

ENDS AND RETURNS TO START OF DISPLAY LOOP.

RETURNS TO DISPLAY LOOP.

ADVANCES TO NEXT MODULE.

240

°F

CNFP

TOP DISPLAY

TEMP/PROCESS

BOTTOM DISPLAY

CNFP/MODULE

1-IN

ENTERS MODULE OR AT CNFP/NO

F1

To access the Configuration Loop, press the up key when F/ is displayed

in the Hidden Loop. The arrow keys are used to select the parameter module

(1-9). To enter a specific module press A while the module number is

displayed. In the Configuration Loop, F will alternate with the parameter

number in the bottom display. The Temperature/Process Value is shown in the

top display.

After entering a parameter module, press A to advance through the

parameter names in the module. To change a parameter’s selection/value, press

the arrow keys while the parameter is displayed. In the modules, the top display

shows the parameter name, and the bottom display shows the selection/value.

Use A to enter any selection/values that have been changed. The change is not

committed to permanent memory until the controller is returned to the Display

Loop. If a power loss occurs before returning to the Display Loop, the new

values must be entered again.

At the end of each module, the controller returns to F/. At this location,

pressing A again returns the display to the the Display Loop. Pressing the Up

key allows re-entrance to the Configuration Loop. Whenever L is pressed, n

momentarily appears as the parameters are stored to permanent memory and the

controller returns to the Display Loop.

FRONT DISPLAY

F1

ENDS AND RETURNS TO START

AT RETURNS TO DISPLAY LOOP.

ADVANCES SELECTION/VALUE.

tYPE

tc-j

TOP DISPLAY

PARAMETER

BOTTOM DISPLAY

SELECTION/VALUE

ADVANCES TO NEXT PARAMETER OR

OF DISPLAY LOOP.

CNFP/NO

12



ALARMS RESET

12

With alarm models, the alarms can be manually reset. The up key resets

Alarm 1 and the down key resets Alarm 2.



ACCESS CODE

1

to

12

If the Access Code is set from -1 to -125, in Lockout Module , Access

Code will appear here. By entering the proper Code, access to the Configuration

Loop is permitted (with a negative Code value, the Hidden Loop can be

accessed without the use of a code). With the factory setting of 0 or with an

active User Input configured for Program Lock (), Access Code will not

appear here. An active user input configured for Program Lock () always

locks out the Configuration Loop, regardless of Access Code.





AUTO-TUNE START





The Auto-Tune procedure of the controller sets the Proportional Band,

Integral Time, Derivative Time, Digital Filter, Control Output Dampening

Time, and Relative Gain (Heat/Cool) values appropriate to the characteristics of

the process. This parameter allows front panel starting  or stopping  of

Auto-Tune. For more information, see PID Tuning Explanations.