Checking the serial port network operation, Stop mode – Vaisala HMP230 User Manual
Page 120

HMP230 SERIES
Appendix 3: RS 485/422 serial port module
M210225en-A
114
4.
CHECKING THE SERIAL PORT NETWORK OPERATION
Normally measurement readings are asked when the transmitter is in POLL
mode; then the command must include the address of the transmitter. If the
settings need to be changed, the transmitter is switched to STOP mode with
command OPEN; commands can then be given without address. When the
line to the transmitter is closed, it returns to POLL mode.
STOP mode
Open the line to the transmitter:
open 22
HMP 22 line opened for operator commands
Transmitter no. 22 is now temporarily set to STOP mode; it accepts com-
mands sent without address until CLOSE command is given. Individual set-
tings can now be easily modified. Do not open more than one line at a time.
Use command ? to find out the settings of the active transmitter:
>?
HMP 230 / 3.01
CPU serial nr
:
S4330008
Keyboard type
:
1
Address
:
0
Output units
:
metric
Baud P D S
:
4800 E 7 1 FDX
Serial mode
:
STOP
Output intrv.
:
0 s
Mtim
:
32
Pressure
:
1013.25
Analog outputs
Ch1
0.00 ...
20.00 mA
Ch2
0.00 ...
20.00 mA
Ch1
( RH )
lo
0.000 %RH
Ch1
( RH )
hi
100.000 %RH
Ch2
( T
)
lo
-40.000 'C
Ch2
( T
)
hi
180.000 'C
Transducer
:
PRB serial nr
:
9702
PRB cal. date
:
970117
When the necessary settings have been made, close the line to transmitters
(the command closes all open lines):
>close
line closed
CLOSE command is always given without address. If no line is open, there
will be no response to the CLOSE commands.