Appendix 2, Obejct property table, Analog input object type (1) – LG PQNFB17B0 User Manual
Page 98: 98 bacnet gateway
Appendix 2
• Analog Input Object Type (1)
Property Identifier
Property Datatype
BACnet
BNU-BAC
Object_Identifier
BACnetObjectIdentifier
R
R
Object_Name
CharacterString
R
R
Object_Type
BACnetObjectType
R
R
Present_Value
Real
R1
R
Description
CharacterString
O
R
Device_Type
CharacterString
O
-
Status_Flags
BACnetStatusFlags
R
R
Event_State
BACnetEventState
R
R
Reliability
BACnetReliability
O
-
Out_Of_Service
BOOLEAN
R
R
Update_Interval
Unsigned
O
-
Units
BACnetEngineeringUnits
R
R
Min_Pres_Value
REAL
O
-
Max_Pres_Value
REAL
O
-
Resolution
REAL
O
-
COV_Increment
REAL
O2
-
Time_Delay
Unsigned
O3
-
Notification_Class
Unsigned
O3
-
High_Limit
Real
O3
-
Low_Limit
Real
O3
-
Deadband
Real
O3
-
Limit_Enable
BACnetLimitEnable
O3
-
Event_Enable
BACnetEventTransitionBits
O3
-
Acked_Transitions
BACnetEventTransitionBits
O3
-
Notify_Type
BACnetNotifyType
O3
-
Event_Time_Stamps
BACnetARRAY[3] of BACnetTimeStamp
O3
-
Profile_Name
CharacterString
O
-
Appendix 2
Obejct Property table
O : indicates that the property is optional.
R : indicates that the property is required to be present and readable using BACnet services.
W : indicates that the property is required to be present, readable, and writable using BACnet
services.
98 BACnet Gateway