Objects (BACnet/IP)
BACnet Point List : Indoor Unit
One indoor unit has the following 22 objects.
Point
No.
Name
ObjectName Product Name
(XXX : Unit address)
Object
Type
Unit
Inactive
Active
Text-0
Text-1
Text-2
Text-3
Text-4
Text-5
1
ON/OFF (Setting)
StartStopCommand_XXX
BO
Stop
Start
2
ON/OFF (Status)
StartStopStatus_XXX
BI
Stop
Run
3
Lock (Setting)
LockCommand_XXX
BO
Permit
Prohibit
4
Lock (Status)
LockStatus_XXX
BI
Permit
Prohibit
5
-
-
-
6
-
-
-
7
Mode (Setting)
ModeCommand_XXX
MO
Cool
Dry
Fan
Auto
Heat
8
Mode (Status)
ModeStatus_XXX
MI
Cool
Dry
Fan
Auto
Heat
9
Swing (Setting)
SwingCommand_XXX
BO
Stop
Run
10
Swing (Status)
SwingStatus_XXX
BI
Stop
Run
11
Fan Speed (Setting)
FanSpeedCommand_XXX
MO
Low
Middle
High
Auto
12
Fan Speed (Status)
FanSpeedStatus_XXX
MI
Low
Middle
High
Auto
13
Set Room Temperature
SetRoomTemp_XXX
AV
°C
14
Room Temperature
RoomTemp_XXX
AI
°C
15
Alarm
Alarm_XXX
BI
Normal
Abnormal
16
Error Code
MalfunctionCode_XXX
AI
Reference LG Original Error Code
17
-
-
-
18
-
-
-
Installation/Owner Manual 55
ENGLISH