Objects (BACnet/IP)
BACnet Point List : Ventilation
One ventilation unit has the following 22 objects.
Point
No.
Name
ObjectName Product Name
(XXX : Unit address)
Object
Type
Unit
Inactive
Active
Text-0
Text-1
Text-2
Text-3
Text-4
Text-5
1
ON/OFF (Setting)
StartStopCommand_XXX
BO
Stop
Start
2
ON/OFF (Status)
StartStopStatus_XXX
BI
Stop
Run
3
Lock (Setting)
LockCommand_XXX
BO
Permit
Prohibit
4
Lock (Status)
LockStatus_XXX
BI
Permit
Prohibit
5
Filter Sign
FilterSign_XXX
BI
Off
On
6
Filter Sign Reset
FilterSignReset_XXX
BV
-
Reset
7
Mode (Setting)
ModeCommand_XXX
MO
Heat
Exchange
Auto
Normal
8
Mode (Status)
ModeStatus_XXX
MI
Heat
Exchange
Auto
Normal
9
-
-
-
10
-
-
-
11
Fan Speed (Setting)
FanSpeedCommand_XXX
MO
Low
High
Super
High
Auto
12
Fan Speed (Status)
FanSpeedStatus_XXX
MI
Low
High
Super
High
Auto
13
-
-
-
14
-
-
-
15
Alarm
Alarm_XXX
BI
Normal
Abnormal
16
Error Code
MalfunctionCode_XXX
AI
Reference LG Original Error Code
17
User Mode (Setting)
UserModeCommand_XXX
MO
Quick Fresh
Energy
Saving
Heater
18
User Mode (Status)
UserModeStatus_XXX
MI
Quick Fresh
Energy
Saving
Heater
Installation/Owner Manual 57
ENGLISH