Modbus point list : indoor unit, Installation/owner manual 65 english – LG PQNFB17B0 User Manual
Page 65
![background image](/manuals/389837/65/background.png)
Objects (Modbus-TCP)
Modbus Point List : Indoor Unit
Function Code : 0x01 and 0x05
Installation/Owner Manual 65
ENGLISH
Address
Register
F
unction Name
Object Name
(XXX : Unit address)
Inactive Active
0x0000 1
Coil Read
ON/OFF StartStopStatus_XXX
Stop
Run
0x0001 2
SWING
SwingStatus_XXX
Permit
Prohibit
0x0002 3
L
OCK
LockStatus_XXX
Permit
Prohibit
0x0003 4
M
ODE
LOCK
ModeLockStatus_XXX
Permit
Prohibit
0x0004 5
FAN
LOCK
WindFlowLockStatus_XXX
Permit
Prohibit
0x0005 6
TEMP
LOCK
SetTempStatus-XXX
Permit
Prohibit
0x0006 7
A
LARM
Alarm_XXX
Normal
Abnormal
0x0000 1
Write Single Coil
ON/OFF StartStopCommand_XXX
Stop
Run
0x0001 2
SWING
SwingCommand_XXX
Permit
Prohibit
0x0002 3
L
OCK
LockCommand_XXX
Permit
Prohibit
0x0003 4
M
ODE
LOCK
ModeLockCommand_XXX
Permit
Prohibit
0x0004 5
FAN
LOCK
WindFlowLockCommand_XXX
Permit
Prohibit
0x0005 6
TEMP
LOCK
SetTempCommand-XXX
Permit
Prohibit