Modbus point list : ahu, Installation/owner manual 69 english – LG PQNFB17B0 User Manual
Page 69
Objects (Modbus-TCP)
Modbus Point List : AHU
Function Code : 0x01 and 0x05
Address
Register
F
unction Name
Object Name
(XXX : Unit address)
Inactive Active
0x0000 1
Coil Read
ON/OFF StartStopStatus_XXX
Stop
Run
0x0001 2
L
OCK
LockStatus_XXX
Permit
Prohibit
0x0002 3
FILTER
SIGN
FilterSign_XXX
Off
On
0x0003 4
S
MOKE
FireAlarmStatus_XXX
Stop
Run
0x0004 5
HUMIDITY
HumidifyStatus_XXX
Stop
Run
0x0005 6
A
UTO
VENT
AutoVentStatus_XXX
Stop
Run
0x0006 7
HUMIDIFIER
HumidifiyUnitStatus-XXX
Stop
Run
0x0007 8
H
EATER
HeaterUnitStatus_XXX
Stop
Run
0x0008 9
VENT
FAN
VentFANStatus_XXX
Stop
Run
0x0009 10
SUPPLY
FAN
SupplyFANStatus_XXX
Stop
Run
0x000A 11
ALARM
Alarm_XXX
Normal
Abnormal
0x0000 1
Write Single Coil
ON/OFF StartStopCommand_XXX
Stop
Run
0x0001 2
L
OCK
LockCommand_XXX
Permit
Prohibit
0x0003 4
S
MOKE
FireAlarmCommand_XXX
Stop
Run
0x0004 5
HUMIDITY
HumidifyCommand_XXX
Stop
Run
0x0005 6
A
UTO
VENT
AutoVentCommand_XXX
Stop
Run
Installation/Owner Manual 69