Objects (modbus-tcp), Supported function code – LG PQNFB17B0 User Manual
Page 64

Objects (Modbus-TCP)
Objects (Modbus-TCP)
Supported Function Code
Monitoring and controlling items of air conditioners supported are assigned with general function
codes specified by Modbus-TCP.
Function Name
Code
Description
Read Coil Status
01h
Run/Stop(status), Lock(status), Swing(status), Alarm, Filter
Sign(status), Mode Lock(status), Wind Flow Lock(status)
Read Holding Registers
03h
Operation Mode(status), Fan Speed(status),
Room Temperature, Error Code,
Set Room Temperature(status),
Set Lower Temperature(status),
Set Upper Temperature(status),
User Mode(status)
Force Single Coil
05h
Run/Stop(setting), Lock(setting), Swing(setting),
Filter Sign Reset, Mode Lock(setting),
Wind Flow Lock(setting)
Preset Single Registers
06h
Operation Mode(setting), Fan Speed(setting),
Set Room Temperature(setting),
Set Lower Temperature(setting),
Set Upper Temperature(setting),
User Mode(setting)
64 Modbus