Objects (Modbus-TCP)
Example of Point Table
The point table below is passed to BMS, and BMS registers the object.
• Case Indoor
• Case Vent
Function Code
Device No.
Product No.
Point
Instance No.
Name
1
0
0
0
0x00000
ON/OFF status
5
0
0
0
0x00000
ON/OFF setting
1
0
1
0
0x00010
ON/OFF status
5
0
1
0
0x00010
ON/OFF setting
1
1
0
0
0x00100
ON/OFF status
5
1
0
0
0x00100
ON/OFF setting
3
0
0
0
0x40000
Mode status
6
0
0
0
0x40000
Mode setting
3
0
1
0
0x40010
Mode status
6
0
1
0
0x40010
Mode setting
3
1
0
0
0x40100
Mode status
6
1
0
0
0x40100
Mode setting
Function Code
Device No.
Product No.
Point
Instance No.
Name
1
0
0
0
0x04000
ON/OFF status
5
0
0
0
0x04000
ON/OFF setting
1
0
1
0
0x04010
ON/OFF status
5
0
1
0
0x04010
ON/OFF setting
1
1
0
0
0x04100
ON/OFF status
5
1
0
0
0x04100
ON/OFF setting
3
0
0
0
0x44000
Mode status
6
0
0
0
0x44000
Mode setting
3
0
1
0
0x44010
Mode status
6
0
1
0
0x44010
Mode setting
3
1
0
0
0x44100
Mode status
6
1
0
0
0x44100
Mode setting
Installation/Owner Manual 73
ENGLISH