Monitoring and Controlling point of indoor and ventilator
Functional Specifications BACnet Gateway
Applicable monitoring and controlling point for the indoor and ventilator are listed below.
Object Name's XX is indoor's address number.
Name
Object Name
Object Type
Indoor
Vent
1
Run/Stop (setting)
StartStopCommand_XXX
Binary Output
O
O
2
Run/Stop (status)
StartStopStatus_XXX
Binary Input
O
O
3
Lock (setting)
LockCommand_XXX
Binary Output
O
O
4
Lock (status)
LockStatus_XXX
Binary Input
O
O
5
Filter Sign
FilterSign_XXX
Binary Input
X
O
6
Filter Sign reset
FilterSignReset_XXX
Binary Value
X
O
7
Operation Mode (setting)
ModeCommand_XXX
Multistate Output
O
O
8
Operation Mode (status)
ModeStatus_XXX
Multistate Input
O
O
9
Swing (setting)
SwingCommand_XXX
Binary Output
O
X
10
Swing (status)
SwingStatus_XXX
Binary Input
O
X
11
Fan speed (setting)
FanSpeedCommand_XXX
Multistate Output
O
O
12
Fan speed (status)
FanSpeedStatus_XXX
Multistate Input
O
O
13
Set Room Temperature
SetRoomTemp_XXX
Analog Value
O
X
14
Room Temperature
RoomTemp_XXX
Analog Input
O
X
15
Alarm
Alarm_XXX
Binary Input
O
O
16
Error Code
MalfunctionCode_XXX
Analog Input
O
O
17
User Mode(setting)
UserModeCommand_XXX
Multistate Output
X
O
18
User Mode(status)
UserModeStatus_XXX
Multistate Input
X
O
19
Set Temperature (status)
SetTempStatus_XXX
Analog Input
O
X
20
Accumulator Power Distribution
(status)
AccumPowerStatus_XXX
Analog Input
O
X
21
AC Operation Mode (setting)
Hrv_ModeCommand_XXX
Multistate Output
X
O
22
AC Operation Mode (status)
Hrv_ModeStatus_XXX
Multistate Input
X
O
23
AC ON/OFF (setting)
HrvStartStopCommand_XX
X
Binary Output
X
O
24
AC ON/OFF (status)
HrvStartStopStatus_XXX
Binary Input
X
O
25
Humidify (setting)
HrvHumidifyCommand_XXX
Binary Output
X
O
26
Humidify (status)
HrvHumidifyStatus_XXX
Binary Input
X
O
27
Set Upper Temperature (setting)
SetUpperTempCommand_X
XX
Analog Value
O
X
28
Set Lower Temperature (setting)
SetLowerTempCommand_X
XX
Analog Value
O
X
29
Set Upper Temperature (status)
SetUpperTempStatus_XXX
Analog Input
O
X
30
Set Lower Temperature (status)
SetLowerTempStatus_XXX
Analog Input
O
X
31
Mode Lock (setting)
ModeLockCommand_XXX
Binary Output
O
X
32
Mode Lock (status)
ModeLockStatus_XXX
Binary Input
O
X
Installation/Owner Manual 51