Objects (BACnet/IP)
Objects (BACnet/IP)
Supported Object Type
Monitoring and controlling items of air conditioners supported are assigned with general object types
specified by BACnet. Support status of each object type is shown in the table below.
(
■ : Supported, ❏ : Unsupported)
Object Type
Supported
Description
Analog Input
0
Room Temperature, Error Code, Set Humidity,
Supply/Outer/Vent/Mixing Temperature,
Supply/Outer/Vent/Mixing Humidity, CO2 Value, Current
OA/EA/Mix Damper, Cool OA/EA/Mix Damper, Heat
OA/EA/Mix Damper, Fan OA/EA/Mix Damper
Analog Value
2
Set Humidity, Cool OA/EA/Mix Damper, Heat OA/EA/Mix
Damper, Fan OA/EA/Mix Damper
Binary Input
3
Run/Stop, Lock, Filter Sign, Swing, Alarm, Humidity,
Auto Ventilation, Humidifier, Heater, Ventilation Fan, Supply
Fan
Binary Output
4
Run/Stop, Lock, Mode Lock, Set Upper/Lower Temperature,
Swing, Humidity, Auto Ventilation
Binary-Value
5
Filter Sign Reset
Calendar
6
Command
7
Device
8
Event-Enrollment
9
File
10
Group
11
Loop
12
Multistate-Output
13
Operation Mode(Setting), Fan Speed(Setting)
User Mode(Setting)
Multistate-Input
14
Operation Mode(Status), Fan Speed(Status)
User Mode(Status)
Notification-Class
15
Program
16
Schedule
17
Averagin
18
Multistate-Value
19
Trend-Log
20
Life-Safety-Point
21
Life-Safety-Zone
22
■
■
■
■
■
❏
❏
■
❏
❏
❏
❏
■
■
❏
❏
❏
❏
❏
❏
❏
❏