60 bacnet gateway – LG PQNFB17B0 User Manual
Page 60
![background image](/manuals/389837/60/background.png)
Objects (BACnet/IP)
Point
No.
Name
ObjectName
Product Name
(XXX : Unit address)
Object
Type
Unit
Inactive
Active
Text-0
Text-1
Text-2
Text-3
Text-4
Text-5
21
Fire Alarm (Status)
FireAlarmStatus_XXX
BI
Stop
Run
22
Set Humidify (Setting)
SethumidifyCommand_XXX
AV
40~60
23
Set Humidify (Status)
SetHumidifyStatus_XXX
AI
40_60
24
Humidify (Setting)
HumidifyCommand_XXX
BO
Stop
Run
25
Humidify (Status)
HumidifyStatus_XXX
BI
Stop
Run
26
Auto Ventilation (Setting)
AutoVentCommand_XXX
BO
Stop
Run
27
Auto Ventilation (Status)
AutoVentStatus_XXX
BI
Stop
Run
28
Supply Temperature (Status)
SupplyTempStatus_XXX
AI
-127~127
29
Outdoor Temperature (Status)
OutdoorTempStatus_XXX
AI
-127~127
30
Mix Temperature (Status)
MixTempStatus_XXX
AI
-127~127
31
Supply Humidity (Status)
SupplyHumidifyStatus_XXX
AI
30~90
32
Outdoor Humidity (Status)
OutdoorHumidifyStatus_XXX
AI
30~90
33
Ventilation Humidity (Status)
VentHumidifyStatus_XXX
AI
30~90
34
CO2 Value (Status)
CO2ValveStatus_XXX
AI
0~255 (Real Value = Value*10, Example : In case Value is 20, CO2 is 20*10=200ppm)
35
Humidify Unit (Status)
HumidifyUnitStatus_XXX
BI
Stop
Run
36
Heater Unit (Status)
HeaterUnitStatus_XXX
BI
Stop
Run
37
Ventilation FAN (Status)
VentFANStatus_XXX
BI
Stop
Run
38
Supply FAN (Status)
SupplyFANStatus_XXX
BI
Stop
Run
39
Current OA Damper (Status)
CurOADamperStatus_XXX
AI
0~90
40
Current EA Damper (Status)
CurEADamperStatus_XXX
AI
0~90
60 BACnet Gateway