Operational maintenance checks, Maintenance schedule, General inspections – Airedale BluCube 10-48kW User Manual
Page 71: Coil guard cleaning, Electrical inspection, Controls alarm log, Condensing units blucube

Condensing Units
BluCube
™
Condensing Units
71
Installation and Maintenance Manual 7222094: 11/2013
Operational Maintenance Checks
Owners Responsibility
To ensure that the unit can be maintained correctly the following requirements are required.
Maintain a safe working environment around the unit, free from obstructions and debris.
The unit shall follow the following maintenance regime as a minimum.
The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work.
Ensure Lock off procedures is carried out accordingly.
Maintenance Schedule
Item
Task
Frequency
Unit Inspection
6 Mths
12 Mths
60 Mths
General Inspections
Check for visible mechanical damage to unit.
Check for cleanliness.
Visually inspect the unit for general wear and tear, treat
metalwork.
Rust should be inhibited, primed and touched up with matching paint.
Check for excess vibration from other rotating equipment.
Coil Guard Cleaning
Ensure that the coil guard is free from debris.
Electrical Inspection
Check main power supply voltages.
Check electrical terminals are tight.
Check that the control panel and fan assembly cables are
securely fastened together.
Check amperages are as per design.
Controls Alarm Log
Check alarm log for any spurious events.
Service tools / Test Equipment
Multimeter
Screwdrivers/ Allen keys
Safety Equipment
Safety Glasses/ Goggles