Electrical data, Heat pump, Condensing units blucube – Airedale BluCube 10-48kW User Manual
Page 49: Condensing units, Electrical data – heat pump
![background image](/manuals/370958/49/background.png)
Condensing Units
BluCube
™
Condensing Units
49
Installation and Maintenance Manual 7222094: 11/2013
Electrical Data
– Heat Pump
CUR092V16-1HP-0
CUR092V20-1HP-0
CUR092V25-1HP-0
Unit Data
(1)
Nominal Run Amps
A
11.5
16.9
19.4
Maximum Start Amps
A
73.7
103.7
145.7
Recommended Mains Fuse Size
A
20
32
32
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Condenser Fan - Motor
Motor Type
AC
AC
AC
1~
1~
1~
Quantity x Motor Size
(2)
kW
1 x 0.6
1 x 0.6
1 x 0.6
Full Load Amps
A
2.7
2.7
2.7
Locked Rotor Amps
A
9.2
9.2
9.2
Compressor
Motor Size
kW
4.6
6.4
8.5
Nominal Run Amps
A
7.9
13.3
15.8
Locked Rotor Amps
A
70
100
142
Type of Start
Direct On Line
OPTIONAL EXTRAS
Electronic Soft-start
Nominal Run Amps
A
11.5
16.9
19.4
Maximum Start Amps
A
45.7
63.7
88.9
Recommended Mains Fuse Size
A
20
32
32
Power Factor Correction
Nominal Run Amps
A
11.2
16.5
18.6
Maximum Start Amps
A
73.7
103.7
145.7
Recommended Mains Fuse Size
A
20
32
32
Compressor Nominal Run Amps
A
7.5
12.9
15
First upgrade EC Motor
1~
1~
1~
Quantity x Motor Size
kW
1 x 0.72
1 x 0.72
1 x 0.72
Full Load Amps
A
3.3
3.3
3.3
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade SCAF
1~
1~
1~
Quantity x Motor Size
kW
1 x 1.4
1 x 1.4
1 x 1.4
Full Load Amps
A
6
6
6
Locked Rotor Amps
A
18
18
18
(1) Based upon ARI conditions, Evaporating at 7°C, Condensing at 54.4°C.