Heat pump cooling modulating capacities, Blucube ™ condensing unit, Condensing units – Airedale BluCube 10-48kW User Manual
Page 42
![background image](/manuals/370958/42/background.png)
BluCube
™
Condensing Unit
42
Condensing Units
Installation and Maintenance Manual : 7222094 11/2013
Heat Pump Cooling Modulating Capacities
Summer Ambient (°C)
25
30
35
40
45
Unit
Evap
Temp
(°C)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
CUR092V16-VHP-0
-5
11.7
4.2
11.7
4.1
11.1
4.5
10.4
4.9
9.7
5.4
0
14.1
4.2
13.9
4.2
13.1
4.7
12.3
5.1
11.5
5.6
5
16.9
4.2
16.3
4.4
15.4
4.8
14.5
5.3
13.4
5.8
7
18.1
4.2
17.4
4.5
16.4
4.9
15.4
5.3
14.3
5.9
10
20.0
4.2
19.0
4.6
18.0
5.0
16.8
5.5
15.6
6.0
CUR092V20-VHP-0
-5
16.0
5.4
15.4
5.6
14.6
6.2
13.7
6.7
N/A
N/A
0
19.1
5.3
18.1
5.9
17.1
6.4
16.0
7.0
14.9
7.7
5
22.2
5.6
21.0
6.1
19.8
6.7
18.6
7.3
17.2
8.0
7
23.5
5.7
22.3
6.2
21.0
6.8
19.7
7.4
18.2
8.1
10
25.5
5.8
24.2
6.4
22.8
7.0
21.4
7.6
19.8
8.4
CUR092V25-VHP-0
-5
19.7
6.3
18.7
7.0
17.5
7.8
16.2
8.6
N/A
N/A
0
23.2
6.6
22.0
7.2
20.6
8.0
19.2
8.8
N/A
N/A
5
26.9
6.9
25.5
7.5
24.0
8.3
22.3
9.1
N/A
N/A
7
28.4
7.0
26.9
7.7
25.3
8.4
23.6
9.2
N/A
N/A
10
30.8
7.2
29.2
7.9
27.4
8.6
25.6
9.5
N/A
N/A
CUR092V29-VHP-0
-5
22.7
7.7
21.3
8.6
19.8
9.5
28.4
10.4
N/A
N/A
0
26.5
8.0
25.0
8.9
23.3
9.9
21.4
10.9
N/A
N/A
5
30.7
8.4
28.9
9.3
26.9
10.2
24.8
11.3
N/A
N/A
7
32.4
8.6
30.5
9.4
28.4
10.4
26.2
11.5
N/A
N/A
10
35.1
8.8
33.0
9.7
30.8
10.6
28.3
11.7
N/A
N/A
CUR122V35-VHP-0
-5
29.5
10.6
28.2
12.2
26.7
13.2
24.9
14.3
N/A
N/A
0
34.8
11.7
33.1
12.6
31.2
13.7
29.2
14.8
26.9
16.0
5
40.4
12.2
38.3
13.1
36.1
14.1
33.6
15.2
31.0
16.4
7
42.8
12.4
40.5
13.3
38.1
14.3
35.5
15.4
32.7
16.6
10
46.5
12.7
44.0
13.6
41.3
14.6
38.5
15.7
35.3
16.9
CUR122V40-VHP-0
-5
34.7
13.5
33.1
14.5
31.4
15.7
29.5
17.0
N/A
N/A
0
40.1
14.0
38.3
15.0
36.2
16.2
33.9
17.5
N/A
N/A
5
46.1
14.5
43.8
15.6
41.3
16.7
38.6
18.0
N/A
N/A
7
48.6
14.7
46.1
15.8
43.5
17.0
40.5
18.3
N/A
N/A
10
52.6
15.1
49.8
16.2
46.8
17.3
43.6
18.6
N/A
N/A
Notes:
1
Output kW refers to the compressor duty.
2