Blucube ™ condensing unit – Airedale BluCube 10-48kW User Manual
Page 52
![background image](/manuals/370958/52/background.png)
BluCube
™
Condensing Unit
52
Condensing Units
Installation and Maintenance Manual : 7222094 11/2013
Electrical Data
– Heat Pump Continued
CUR092V29-VHP-0
CUR122V35-VHP-0
CUR122V40-VHP-0
Unit Data
(1)
Nominal Run Amps
A
20.4
25.5
30.8
Maximum Start Amps
A
121.7
144.4
177.4
Recommended Mains Fuse Size
A
32
40
50
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Condenser Fan - Motor
Motor Type
AC
AC
AC
1~
3~
3~
Quantity x Motor Size
(2)
kW
1 x 0.6
1 x 1.97
1 x 1.97
Full Load Amps
A
2.7
3.4
3.4
Locked Rotor Amps
A
9.2
11.9
11.9
Compressor
Motor Size
kW
9.4
11.8
13.9
Nominal Run Amps
A
16.8
21.1
26.4
Locked Rotor Amps
A
118
140
173
Type of Start
Direct On Line
OPTIONAL EXTRAS
Electronic Soft-start
Nominal Run Amps
A
20.4
25.5
30.8
Maximum Start Amps
A
74.5
88.4
108.2
Recommended Mains Fuse Size
A
32
40
50
Power Factor Correction
Nominal Run Amps
A
N/A
N/A
N/A
Maximum Start Amps
A
N/A
N/A
N/A
Recommended Mains Fuse Size
A
N/A
N/A
N/A
Compressor Nominal Run Amps
A
N/A
N/A
N/A
First upgrade EC Motor
1~
3~
3~
Quantity x Motor Size
kW
1 x 0.72
1 x 1.85
1 x 1.85
Full Load Amps
A
3.3
2.9
2.9
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade SCAF
1~
3~
3~
Quantity x Motor Size
kW
1 x 1.4
1 x 1.94
1 x 1.94
Full Load Amps
A
6
3.4
3.4
Locked Rotor Amps
A
18
11.9
11.9
(1) Based upon ARI conditions, Evaporating at 7°C, Condensing at 54.4°C.