Installation and Maintenance Manual 7222094: 11/2013

Electrical Data

– Cooling Only Continued

CUR092V29-1CO-0

CUR122V35-1CO-0

CUR122V40-1CO-0

Unit Data

(1)

Nominal Run Amps

A

20.6

25.1

29

Maximum Start Amps

A

145.7

162.4

201.4

Recommended Mains Fuse Size

A

32

40

50

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Condenser Fan - Motor

Motor Type

AC

AC

AC

1~

3~

3~

Quantity x Motor Size

kW

1 x 0.6

1 x 1.97

1 x 1.97

Full Load Amps

A

2.7

3.4

3.4

Locked Rotor Amps

A

9.2

11.9

11.9

Compressor

Motor Size

kW

9.5

12.2

13.8

Nominal Run Amps

A

17

20.7

24.6

Locked Rotor Amps

A

142

158

197

Type of Start

Direct On Line

OPTIONAL EXTRAS

Electronic Soft-start

Nominal Run Amps

A

20.6

23.8

27.5

Maximum Start Amps

A

88.9

99.2

122.6

Recommended Mains Fuse Size

A

32

40

50

Power Factor Correction

Nominal Run Amps

A

19.8

23.8

29

Maximum Start Amps

A

145.7

162.4

201.4

Recommended Mains Fuse Size

A

32

40

50

Compressor Nominal Run Amps

A

16.2

19.4

23.1

First upgrade EC Motor

1~

3~

3~

Quantity x Motor Size

kW

1 x 0.72

1 x 1.85

1 x 1.85

Full Load Amps

A

3.3

2.9

2.9

Locked Rotor Amps

A

N/A

N/A

N/A

Second upgrade SCAF

1~

N/A

N/A

Quantity x Motor Size

kW

1 x 1.4

N/A

N/A

Full Load Amps

A

6

N/A

N/A

Locked Rotor Amps

A

18

N/A

N/A

(1) Based upon ARI conditions, Evaporating at 7°C, Condensing at 54.4°C.