Condensing units blucube – Airedale BluCube 10-48kW User Manual
Page 35
Condensing Units
BluCube
™
Condensing Units
35
Installation and Maintenance Manual 7222094: 11/2013
Electrical Data
– Cooling Only Continued
CUR092V29-1CO-0
CUR122V35-1CO-0
CUR122V40-1CO-0
Unit Data
(1)
Nominal Run Amps
A
20.6
25.1
29
Maximum Start Amps
A
145.7
162.4
201.4
Recommended Mains Fuse Size
A
32
40
50
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Condenser Fan - Motor
Motor Type
AC
AC
AC
1~
3~
3~
Quantity x Motor Size
kW
1 x 0.6
1 x 1.97
1 x 1.97
Full Load Amps
A
2.7
3.4
3.4
Locked Rotor Amps
A
9.2
11.9
11.9
Compressor
Motor Size
kW
9.5
12.2
13.8
Nominal Run Amps
A
17
20.7
24.6
Locked Rotor Amps
A
142
158
197
Type of Start
Direct On Line
OPTIONAL EXTRAS
Electronic Soft-start
Nominal Run Amps
A
20.6
23.8
27.5
Maximum Start Amps
A
88.9
99.2
122.6
Recommended Mains Fuse Size
A
32
40
50
Power Factor Correction
Nominal Run Amps
A
19.8
23.8
29
Maximum Start Amps
A
145.7
162.4
201.4
Recommended Mains Fuse Size
A
32
40
50
Compressor Nominal Run Amps
A
16.2
19.4
23.1
First upgrade EC Motor
1~
3~
3~
Quantity x Motor Size
kW
1 x 0.72
1 x 1.85
1 x 1.85
Full Load Amps
A
3.3
2.9
2.9
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade SCAF
1~
N/A
N/A
Quantity x Motor Size
kW
1 x 1.4
N/A
N/A
Full Load Amps
A
6
N/A
N/A
Locked Rotor Amps
A
18
N/A
N/A
(1) Based upon ARI conditions, Evaporating at 7°C, Condensing at 54.4°C.