Heat pump heating modulating capacities, Blucube ™ condensing unit, Condensing units – Airedale BluCube 10-48kW User Manual
Page 44
BluCube
™
Condensing Unit
44
Condensing Units
Installation and Maintenance Manual : 7222094 11/2013
Heat Pump Heating Modulating Capacities
Winter Ambient (°C)
-5
0
5
10
15
Unit
Cond
Temp
(°C)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
Output
(kW)
Input
(kW)
CUR092V16-VHP-0
40
12.1
4.4
13.6
4.4
15.2
4.5
17.0
4.5
18.9
4.6
45
12.1
4.8
13.6
4.9
15.1
5.0
16.8
5.0
18.6
5.1
50
N/A
N/A
13.5
5.4
15.0
5.5
16.6
5.5
18.3
5.6
55
N/A
N/A
N/A
N/A
14.8
6.0
16.4
6.1
18.0
6.2
CUR092V20-VHP-0
40
15.9
5.7
17.7
5.8
19.6
5.9
21.7
5.9
23.9
6.0
45
15.9
6.2
17.7
6.4
19.5
6.5
21.5
6.5
23.7
6.6
50
N/A
N/A
17.6
7.0
19.4
7.1
21.4
7.2
23.4
7.3
55
N/A
N/A
N/A
N/A
N/A
N/A
21.2
8.0
23.2
8.1
CUR092V25-VHP-0
40
19.0
7.0
21.0
7.0
23.2
7.0
25.5
7.0
28.0
7.0
45
19.1
7.9
21.1
7.8
23.2
7.8
25.4
7.7
27.8
7.7
50
N/A
N/A
21.1
8.8
23.2
8.7
25.3
8.6
27.7
8.6
55
N/A
N/A
N/A
N/A
N/A
N/A
25.3
9.7
27.5
9.6
CUR092V29-VHP-0
40
21.6
8.2
23.9
8.2
26.4
8.1
29.0
8.1
31.7
8.1
45
21.7
9.2
24.0
9.2
26.4
9.1
28.9
9.1
31.6
9.1
50
N/A
N/A
N/A
N/A
26.5
10.2
28.9
10.2
31.4
10.1
55
N/A
N/A
N/A
N/A
N/A
N/A
28.9
11.5
31.3
11.4
CUR122V35-VHP-0
40
27.9
12.3
31.0
12.4
34.5
12.4
37.9
12.5
41.8
12.6
45
28.1
13.4
31.1
13.5
34.5
13.5
37.8
13.6
41.6
13.7
50
N/A
N/A
N/A
N/A
34.4
14.8
37.7
14.8
41.3
14.9
55
N/A
N/A
N/A
N/A
N/A
N/A
37.5
16.2
40.9
16.3
CUR122V40-VHP-0
40
32.7
14.1
36.0
14.2
39.8
14.3
43.4
14.3
47.6
14.4
45
33.0
15.4
36.3
15.4
39.9
15.5
43.5
15.6
47.4
15.7
50
N/A
N/A
N/A
N/A
40.0
16.9
43.5
17.0
47.3
17.0
55
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
47.0
18.6
Notes:
1
Output kW refers to the compressor duty.
2