BluCube

Condensing Unit

70

Condensing Units

Installation and Maintenance Manual : 7222094 11/2013

Troubleshooting

FAULT

POSSIBLE CAUSE

REMEDY / ACTION

Condenser fan runs too fast High ambient condition or excessive re-

circulation of air around condenser coil.

Check installation against design.

Minimum set speed setting incorrect.

Adjust as necessary.

Incorrect pressure sensor setting.

Adjust sensor screw as necessary.

Faulty Fan Speed Controller.

Replace controller and sensor (as they are
matched sets).

Faulty pressure sensor.

Replace controller and sensor (as they are
matched sets).

Condenser fans runs only
slowly

Incorrect pressure setting.

Adjust sensor screw as necessary.

Faulty Controller.

Replace controller and sensor (as they are
matched sets).

Faulty Pressure sensor.

Replace controller and sensor (as they are
matched sets).

Motor/capacitor faulty.

Replace.